Installation, Operation and Maintenance Manual
IO-70103 RevE 08-17
4
WARNING!
INDICATE[S] A HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, COULD RESULT IN DEATH OR SERIOUS INJURY. WARNING
[SIGNS] SHOULD NOT BE USED FOR PROPERTY DAMAGE HAZARDS UNLESS PERSONAL INJURY
RISK APPROPRIATE TO THIS LEVEL IS ALSO INVOLVED.
AVERTISSEMENT!
INDIQUE UNE SITUATION DANGEREUSE QUI, SI ELLE N’EST PAS ÉVITÉE,
POURRAIT ENTRAÎNER LA MORT OU DES BLESSURES GRAVES. LES SIGNES AVERTISSEMENT NE
DOIVENT PAS ÊTRE UTILISÉS POUR LES RISQUES DE DOMMAGES À LA PROPRIÉTÉ, SAUF SI LE
RISQUE DE BLESSURES APPROPRIÉES À CE NIVEAU EST ÉGALEMENT IMPLIQUÉ.
CAUTION!
INDICATE[S] A HAZARDOUS SITUATION WHICH, IF NOT
AVOIDED, COULD RESULT IN MINOR OR MODERATE INJURY. CAUTION
[SIGNS] WITHOUT A SAFETY ALERT SYMBOL MAY BE USED TO ALERT AGAINST UNSAFE
PRACTICES THAT CAN RESULT IN PROPERTY DAMAGE ONLY.
ATTENTION!
INDIQUE UNE SITUATION DANGEREUSE QUI, SI ELLE N’EST PAS ÉVITÉE, POURRAIT
ENTRAÎNER DES BLESSURES MINEURES OU MODÉRÉES. LES SIGNES ATTENTION SANS SYMBOLE
D’ALERTE DE SÉCURITÉ PEUVENT ÊTRE UTILISÉS POUR METTRE EN GARDE CONTRE DES
PRATIQUES DANGEREUSES QUI PEUVENT ENTRAÎNER DES DOMMAGES MATÉRIELS SEULEMENT.
ELECTRICAL CONNECTIONS
All wiring must comply with the National Electrical Code (NEC) and applicable local codes.
DANGER!
ONLY QUALIFIED PERSONNEL SHOULD INSTALL OR
SERVICE THIS SYSTEM. ELECTRICAL SAFETY PRE-CAUTIONS MUST
BE FOLLOWED WHEN INSTALLING OR SERVICING THIS EQUIPMENT. TO PREVENT RISK OF
ELECTRICAL SHOCK, TURN OFF AND LOCK OUT ALL POWER SOURCES TO THE UNIT BEFORE
MAKING ELECTRICAL CONNECTIONS OR SERVICING.
DANGER!
SEULEMENT LE PERSONNEL QUALIFIÉ DOIT INSTALLER OU MAINTENIR CE SYSTÈME. DES
PRÉCAUTIONS DE SÉCURITÉ EN ÉLECTRICITÉ DOIVENT ÊTRE SUIVIS LORS DE L’INSTALLATION OU
DE LA MAINTENANCE DE CET EQUIPEMENT. POUR EVITER TOUT RISQUE DE CHOC ÉLECTRIQUE,
DÉBRANCHEZ ET VEROUILLER TOUTES LES SOURCES D’ ALIMENTATION DE CET EQUIPEMENT
AVANT DE LE BRANCHER OU LE MAINTENIR.
Voltage Ratings and Power Source Configurations:
Before making connections to the unit, verify that
the unit model number and nameplate voltage rating are appropriate for connection to the intended power
source. See the chart on page 3 for voltage rating applications with typical power source configurations.
Wire Connections:
With parallel connection, the size of the wiring to the SPD unit is independent of the
protected circuit’s ampacity. NEC Article 285-21(B) requires surge suppressor connecting conductors
to be at least #14 copper or #12 aluminum. To reduce the wiring impedance to surge currents, it is
recommended that the phase, neutral (if required), and ground conductors are twisted together and
routed in the same raceway (conduit). Avoid any sharp bends in the conductors.
Overcurrent Protection:
The SPD unit conducts practically no current under normal operation and only
conducts very short duration transient surge currents.