Installation, Operation and Maintenance Manual
IO-70103 RevE 08-17
12
MODEL 515 - Suggested Circuit Breaker And Wire Size
Overcurrent Protection
(Circuit Breaker):
Allowable Range: 15A - 100A
Suggested Size: 30A
Connection Wire:
Allowable Range: #14 - #2
Suggested Size: #10
Weight
:
30 lb. (13.6 kg)
Summary Alarm Contacts:
Connection shall be with
#18 – 22 AWG. Form ‘C’
contacts are rated 5 amps at
250 VAC max.
DIMENSIONAL INFORMATION
A
18” [457]
B
12” [305]
C
6” [152]
D
11” [279]
E
15” [381]
F
20.25” [514]
G
21.5” [546]
515 SPD
Panelboard
Extension
Customer
Supplied
Panelboard
A
G (FLUSH)
F (SURFACE)
E
B
D
C
With AC Applied
NC = Normally Open
COM = Common
NO = Normally Closed
Shown with cover removed