© 2020 ASCO Power Technologies. All Rights Reserved
For troubleshooting, call technical assistance at 1-800-237-4567 or [email protected]
23
IO-70064
05/2020
The dry contacts are designed for a maximum voltage of 24 Vdc / 24 Vac
and a maximum current of 2 A. For application questions, contact the ASCO
Power Technologies Technical Assistance Group at (800) 237-4567 or
Maintenance and
Troubleshooting
Preventative Maintenance
Troubleshooting
Replacement Parts
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, CSA Z462 or NOM-029-STPS.
•
This equipment must only be installed and serviced by qualified
electrical personnel.
•
Turn off all power supplying this equipment before working on or inside
equipment.
•
Always use a properly rated voltage sensing device to confirm power is
off.
• Replace all devices, doors and covers before turning on power to this
equipment.
•
This equipment must be effectively grounded per all applicable codes.
Use an equipment-grounding conductor to connect this equipment to the
power system ground.
Failure to follow these instructions will result in death or serious injury.
Inspect the SPD periodically to hlep maintain system performance and
continued transient voltage surge suppression. Periodically check the state
of the diagnostic display panel LED status indicators. Routinely use the built-
in diagnostics to inspect for inoperative modules.
The ASCO 460/465/480/485 surge protector has little to troubleshoot. If a
phase LED in extinguished or the service light is on please contact ASCO
Power Technologies. For application questions, contact the ASCO Power
Technologies Technical Assistance Group at (800) 237-4567 or surgetech@
ascopower.com
The module(s) is field replaceable. Deenergize SPD, confirm with
appropriate measurement equipment and discharge internal capacitance
to ground. Mark locations and carefully disconnect diagnostic cables,
dry contact connections, phase conductors, unplug parallel connections
between modules. Depending on model, module may be bolted to backplane
or the backplane may be part of the module assembly. Remove module/
backplane. Reinstall in reverse order.
There are no user serviceable parts inside the module. We strongly
recommend against disassembly. Modules may be returned to the factory for
factory service, qualification and return. Please contact the factory at (800)
237-4567 for assistance.
DANGER
ASCO 460/465/480/485 Surge Protective Device (SPD)
Maintenance and Troublesheeting