background image

© 2020 ASCO Power Technologies. All Rights Reserved

For troubleshooting, call technical assistance at 1-800-237-4567 or [email protected]

8

IO-70061

01/2020

ASCO 430 Surge Protective Device (SPD)

Electrical

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

Confirm the surge protective device voltage rating on the module or 

 

nameplate label is not less than the operating voltage.

Failure to follow these instructions will result in death or serious injury.

Prior to mounting the SPD, verify that the device has the same voltage 

rating as the power distribution system in which it is installed. Compare the 

nameplate voltage or model number on the SPD with the nameplate of the 

electrical distribution equipment.

The specifier or user of the device should be familiar with the configuration 

and arrangement of the power distribution system in which the SPD is to be 

installed. The system configuration of any power distribution system is based 

strictly on how the secondary windings of the transformer supplying the ser-

vice entrance main or load are configured. This includes whether or not the 

transformer windings are referenced to earth via a grounding conductor. The 

system configuration is not based on how any specific load or equipment 

is connected to a particular power distribution system. See Table 1 for the 

service voltage of each SPD.

Electrical

Voltage Rating

Table 1: 

Model 430 Service Voltages

DANGER



Voltage Codes

P



C

J

A

Per Phase 

kA Rating 

System

Modes of 

Protection

(Default)

Connection 

Type

Monitoring 

Options

Enclosure

UL 1449

Type1/Type 2

0

Option(s)

kA Rating 

Per Phase

430

Model 430

Product Line

J = NEMA 4X Non-Metallic

(Polycarbonate)

Size - 6” x 6” x 4”

C = Compression 

Lugs

S = LEDs
A = LEDs/Audible Alarm/Relay

1 = UL 1449 Type 1
2 = UL 1449 Type 2, 

(Includes UL1283 

Filter)

10 = 100kA
15 = 150kA
20 = 200kA

120S = 120/240V Split Phase - 1Ø, 3W+Grnd
120Y = 208Y/120V Wye - 3Ø 4W+Grnd

240H = 240/120V High Leg Delta (B High)

277Y = 480Y/277V Wye - 3Ø 4W+Grnd
347Y = 600Y/347V Wye - 3Ø 4W+Grnd

480D = 480V Delta - 3Ø 3W+Grnd & HRG Wye
120N = 120V Single Phase
127N = 127V Single Phase

127S = 127/254V Split Phase - 1Ø 3W+Grnd
127Y = 220Y/127V Wye - 3Ø 4W+Grnd
220Y = 380Y/220V Wye - 3Ø 4W+Grnd 
230Y = 400Y/230V Wye - 3Ø 4W+Grnd

240N = 240V Single Phase - Not split phase

240S = 240/480V Split Phase - 1Ø, 3W+Grnd
240Y = 415Y/240V Wye - 3Ø 4W+Grnd 

240C = 240V B Corner Grnd Delta, 3Ø 3W+Grnd 
240D = 240V Delta - 3Ø 3W+Grnd 

254Y = 440Y/254V Wye - 3Ø 4W+Grnd 

277N = 277V Single Phase
300N = 300V Single Phase

300Y = 520Y/300V Wye - 3Ø 4W+Grnd

480N = 480V Single Phase (1 Hot, 1 Neu, 1 Grnd)
480C = 480V B Corner Grnd Delta, 3Ø 3W+Grnd
600C = 600V B Corner Grnd Delta, 3Ø 3W+Grnd

600D = 600V Delta - 3Ø 3W+Grnd & HRG Wye

Содержание 430

Страница 1: ...Surge Protective Devices Installation Operation Manual Model 430 ...

Страница 2: ... 2020 ASCO Power Technologies All Rights Reserved For troubleshooting call technical assistance at 1 800 237 4567 or customercare ascopower com 2 IO 70061 01 2020 ...

Страница 3: ...Noise Mounting Service Clearance Equipment Performance Electrical Voltage Rating Branch Circuit Overcurrent Protection and Disconnect Means Location of Surge Protective Device SPD System Grounding Wiring ASCO 430 Wiring Diagrams Installation Surface Mount Installation Flush Mount Installation Operation LED Status Indicators Audible Alarm Dry Contacts Remote Monitor Option Preventive Maintenance 3 ...

Страница 4: ...nal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a hazardous situation which if not avoided could result i...

Страница 5: ... is known to the State of California to cause birth defects or other reproductive harm For more information go to www P65Warnings ca gov NOTICE LOSS OF BRANCH CIRCUIT POWER LOSS OF SURGE SUPPRESSION Perform periodic inspection of the surge protective device status indicator lights as part of the preventative maintenance schedule Promptly replace the surge protective device when an alarm state exis...

Страница 6: ... STPS or CSA Z462 This equipment must only be installed and serviced by qualified electrical personnel Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicabl...

Страница 7: ...relative humidity of 0 to 95 non condensing This device has a Type 4X housing The device background noise is negligible and does not restrict the location of the installation The device has been designed to be surface mounted An additional flush mount kit is also available if required KITFMXF or stainless steel flush mount kit KITFMXFSS The service clearance should meet all applicable code require...

Страница 8: ...how any specific load or equipment is connected to a particular power distribution system See Table 1 for the service voltage of each SPD Electrical Voltage Rating Table 1 Model 430 Service Voltages DANGER Voltage Codes P C J A Per Phase kA Rating System Modes of Protection Default Connection Type Monitoring Options Enclosure UL 1449 Type1 Type 2 0 Option s kA Rating Per Phase 430 Model 430 Produc...

Страница 9: ... ASCO 430 device per applicable state and local building codes UL 1449 Type 1 SPDs have been designed and approved for line side appli cations prior to the main service disconnect without supplemental overcur rent protection Type 2 SPDs must be installed on the load side of the main Overcurrent Protective Device OCPD All installations should either provide or include a disconnecting means Type 1 S...

Страница 10: ...tions will result in death or serious injury NOTICE LOSS OF SURGE SUPPRESSION Verify that the service entrance equipment is bonded to ground in accordance with all applicable codes Failure to follow these instructions can result in equipment damage The ASCO 430 has SPD elements connected from phase to ground It is critical that there be a robust and effective connection to the building grounding s...

Страница 11: ...rehensive electrical maintenance program Failure to follow these instructions can result in equipment damage HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH Apply appropriate personal protective equipment PPE and follow safe electrical work practices See NFPA 70E NOM 029 STPS or CSA Z462 This equipment must only be installed and serviced by qualified electri cal personnel Turn off all power supply...

Страница 12: ...ry twelve inches of length 6 Do not loop or coil wires Be sure to maintain adequate wire bending space per NEC 7 Use on solidly grounded systems unless the SPD model is designed for installation on ungrounded HRG systems HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH For outdoor installation use and appropriate weather sealing at the nipple o ring sealing conduit etc Failure to follow these instr...

Страница 13: ... Installation Figure 7 Single Phase Two Wire Ground V Neutral White Phase A Black Ground Green CONTACTS NO C NC DRY SERVICE A C B N G Installation Operation and Maintenance Manual IO 70061 RevJ 09 18 A B C G N BREAKER Use closest breaker to SPD Locate SPD close to intended breaker Keep Leads Short as Possible Avoid Sharp Bends Rotate Model 430 such that LED indicator is most visible Outdoor instal...

Страница 14: ...ng Note 1 The neutral conductor is not present on three wire Wye grounded power systems For improved operation of the SPD bond the neutral and ground lugs together inside the SPD Phase A Black Phase C Black Ground Green V CONTACTS NO C NC DRY SERVICE A C TWO POLE A C G HAZARD OF ELECTRIC SHOCK EXPLOSION OR ARC FLASH The high leg of the power system must connect to the B phase lug of the SPD Failur...

Страница 15: ...nside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equipment grounding conductor to connect this equipment to the power system ground Failure to follow these instructions will result in death or serious in...

Страница 16: ... the unit will be supported from its back 3 Configure the electrical conductor and conduit connection consistent with the installation instructions on pages 9 through 13 Preplan connections such that they are completed prior to fastening the unit to the backing plate 4 Install faceplate cover applying a torque of 5 lb in 0 5 N m to the four screws prior to energizing and testing the unit Flush Mou...

Страница 17: ...and Audible alarm ON Loss of surge suppresion Indicator light ON red loss of surge suppresion The audible alarm does not have a silence switch Silence the alarm by removing power from the SPD The alarm indicates that the device needs replacement by qualified electrical personnel INADEQUATE DRY CONTACT USE Do not supply more than 24 Vdc 24 Vac and no more than a current of 2 A Failure to follow the...

Страница 18: ...d an audible alarm with an enable disable switch Normal status is a lit green LED and no audible alarm To test the integrity of the remote monitor press the push to test switch The green LED will turn off the red LED will turn on and the alarm will sound if the alarm is enabled Releasing the switch will complete the test the red LED will turn off the green LED will turn on and the alarm will shut ...

Страница 19: ...his equipment must only be installed and serviced by qualified electri cal personnel Turn off all power supplying this equipment before working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equ...

Страница 20: ...nd completeness in this literature Schneider Electric assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions 14550 58th Street North Clearwater Florida 33760 se com us en work support 1 888 778 2733 ...

Отзывы: