Figure 12: Flush Mount
Step 1:
Prepare wall
and SPD
Step 2:
Insert into
wall
Step 3:
Mount the
SPD
Step 4:
Mount
the lid
Wall cutout
font view
6 1/6 in.
(154 mm)
6 3/4 in.
(171 mm)
6.75 in.
(171 mm)
Wall opening
Wide
Tall
Note:
Supplemental instructions for deep wall mounting (walls over 4 in. (101 mm) thick using the enclosed mounting feet.
Mounting plate
installed
3 15/16 in.
(100 mm) from
the front wall.
Flexible
conduit
Flexible
conduit
Flexible
conduit
Mounting
plate
in.
(mm)
ASCO 430 Surge Protective Device (SPD)
Operation
Note:
Mount the unit as close as possible to the protected panel.
1. Create a wall opening 6 3/4 in. x 6 1/16 in. and 3 15/16 in. of clearance.
See Figure 12. (Rotate dimensions 90° as appropriate depending on
orientation).
2.
Configure an appropriate backing plate inside the wall cavity 3 15/16
inches from the wall face such that the unit will be supported from its
back.
3.
Configure the electrical conductor and conduit connection consistent with
the installation instructions on pages 9 through 13. Preplan connections
such that they are completed prior to fastening the unit to the backing
plate.
4. Install faceplate/cover, applying a torque of 5 lb-in (0.5 N•m) to the four
screws, prior to energizing and testing the unit.
Flush Mount Installation
Operation
Figure 12:
Flush Mount
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.
•
This equipment must only be installed and serviced by qualified electri
-
cal personnel.
•
Turn off all power supplying this equipment before working on or inside
equipment.
•
Always use a properly rated voltage sensing device to confirm power is
off.
• Replace all devices, doors and covers before turning on power to this
equipment.
•
This equipment must be effectively grounded per all applicable codes.
Use an equipment-grounding conductor to connect this equipment to the
power system ground.
Failure to follow these instructions will result in death or serious injury.
DANGER