Installation
•
Turn off all power supplying this equipment before working on or inside
equipment.
For 160D006S20KXCXN0 Head-End Equipment:
1. Connect the 160D006S20KXCXN0 in line with the coaxial cable.
Connect the side labeled “EQUIP” to the adjacent head-end equipment.
2. Connect incoming coaxial cable to the side of the 160D006S20KXCXN0
labeled “CABLE”.
3. Connect a ground wire (10-12 AWG) between the 160D006S20KXCXN0
ground terminal and the AC power ground of head-end equipment.
Keep this wire as short and straight as possible.
For 160D006S20KXCGN0 and 160D006S20KXCGL0 Camera-End
Protection (with Isolated Ground):
1. Connect the 160D006S20KXCGN0 or 160D006S20KXCGL0 in line with
the coaxial cable. Connect the side labeled “EQUIP” to the adjacent
camera.
2. Connect incoming coaxial cable to the side of the ASCO
160D006S20KXCGN0 or 160D006S20KXCGL0 labeled “CABLE”.
3. Connect a ground wire (10-12 AWG) between the ASCO
160D006S20KXCGN0 or 160D006S20KXCGL0 ground terminal and
either the AC power ground or equipment building ground at the camera
location. Keep this wire as short and straight as possible.
For 160D006S20KX16N0 Rack Mount Unit:
1. The ASCO Model 160 is designed to be installed in a standard 19”
equipment rack and take up 1 unit (1U) of space. Secure unit to rack
using the four slots and four screws (not provided).
2. Connect ground wire #12-6 AWG using a #10 ring terminal from the
ground stud on backside of unit to an approved building ground. Wire
must be short and as straight as possible.
3. Connect incoming wire from video equipment to a BNC connector on
marked “IN” on front of the Model 160.
4. Complete the circuit by connecting from the corresponding BNC
connector marked “OUT” to the video camera.
•
Replace the barrier, cover/door and/or trim to the equipment.
•
Equipment may be re-energized after all the above steps are complete.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• These protectors are intended for indoor use on communication loop
circuits which have been isolated from the Public Switch Telephone
Network.
• Do not expose the communication loop to contact with the electric light
or power conductors.
• Install the protectors as per the applicable requirements of the National
Electric Code, ANSI/NFPA 70.
Failure to follow these instructions will result in death or serious
injury.
ASCO Model 160 (EDCO CX and RM-CX Series)
Surge Protectective Device (SPD)
DANGER