Asco 160 Скачать руководство пользователя страница 4

© 2020 ASCO Power Technologies. All Rights Reserved

4

IO-75025

01/2020

For access to self-service tools and chat support visit se.com/us/en/work/support  or call 1-888-778-2733 for technical assistance

Installation

• 

Turn off all power supplying this equipment before working on or inside 

equipment.

For 160D006S20KXCXN0 Head-End Equipment:

1.  Connect the 160D006S20KXCXN0 in line with the coaxial cable. 

Connect the side labeled “EQUIP” to the adjacent head-end equipment.

2.  Connect incoming coaxial cable to the side of the 160D006S20KXCXN0 

labeled “CABLE”.

3.  Connect a ground wire (10-12 AWG) between the 160D006S20KXCXN0 

ground terminal and the AC power ground of head-end equipment. 

Keep this wire as short and straight as possible.

For 160D006S20KXCGN0 and 160D006S20KXCGL0 Camera-End 

Protection (with Isolated Ground):

1.  Connect the 160D006S20KXCGN0 or 160D006S20KXCGL0 in line with 

the coaxial cable. Connect the side labeled “EQUIP” to the adjacent 

camera.

2.  Connect incoming coaxial cable to the side of the ASCO 

160D006S20KXCGN0 or 160D006S20KXCGL0 labeled “CABLE”.

3.  Connect a ground wire (10-12 AWG) between the ASCO 

160D006S20KXCGN0 or 160D006S20KXCGL0 ground terminal and 

either the AC power ground or equipment building ground at the camera 

location. Keep this wire as short and straight as possible.

For 160D006S20KX16N0 Rack Mount Unit:

  

1.  The ASCO Model 160 is designed to be installed in a standard 19” 

equipment rack and take up 1 unit (1U) of space. Secure unit to rack 

using the four slots and four screws (not provided).

2.  Connect ground wire #12-6 AWG using a #10 ring terminal from the 

ground stud on backside of unit to an approved building ground. Wire 

must be short and as straight as possible.

3.  Connect incoming wire from video equipment to a BNC connector on 

marked “IN” on front of the Model 160.

4.  Complete the circuit by connecting from the corresponding BNC 

connector marked “OUT” to the video camera.

• 

Replace the barrier, cover/door and/or trim to the equipment.

• 

Equipment may be re-energized after all the above steps are complete.

HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH

•  These protectors are intended for indoor use on communication loop 

circuits which have been isolated from the Public Switch Telephone 

Network.

•  Do not expose the communication loop to contact with the electric light 

or power conductors.

•  Install the protectors as per the applicable requirements of the National 

Electric Code, ANSI/NFPA 70.

Failure to follow these instructions will result in death or serious 

injury.

ASCO Model 160 (EDCO CX and RM-CX Series)

Surge Protectective Device (SPD)

DANGER

Содержание 160

Страница 1: ...Surge Protective Devices Installation Operation Manual Model 160 160D006S20KXCXN0 Edco CX06 M 160D006S20KXCGN0 Edco CX06 MI 160D006S20KXCGL0 Edco CX06 MI SBL 160D006S20KX16N0 Edco RM CX06 16R ...

Страница 2: ...lert symbol It is used to alert you to potential personal injury hazards Obey all safety messages that follow this symbol to avoid possible injury or death DANGER DANGER indicates a hazardous situation which if not avoided will result in death or serious injury WARNING WARNING indicates a hazardous situation which if not avoided could result in death or serious injury CAUTION CAUTION indicates a h...

Страница 3: ... working on or inside equipment Always use a properly rated voltage sensing device to confirm power is off Replace all devices doors and covers before turning on power to this equipment This equipment must be effectively grounded per all applicable codes Use an equipment grounding conductor to connect this equipment to the power system ground Confirm that the Surge Protective Device voltage rating...

Страница 4: ... ground or equipment building ground at the camera location Keep this wire as short and straight as possible For 160D006S20KX16N0 Rack Mount Unit 1 The ASCO Model 160 is designed to be installed in a standard 19 equipment rack and take up 1 unit 1U of space Secure unit to rack using the four slots and four screws not provided 2 Connect ground wire 12 6 AWG using a 10 ring terminal from the ground ...

Страница 5: ...technical assistance Figure 1 Connection Diagram ASCO Model 160 EDCO CX and RM CX Series Surge Protectective Device SPD Head End Equipment Camera End Equipment To AC Power Ground Keep ground wire as short as possible Keep ground wire as short as possible To AC Power Ground or Building Ground Model 160D006S20KXCGN0 Model 160D006S20KXCXN0 or 160D006520KX16NO 16 Channel Rackmount ...

Страница 6: ...e 0 to 20 MHz Insertion Loss 0 1 dB at 20 MHz Response Time 0 5 ns SPD Technology GDT SAD w Series PTC Connection Type BNC 50 75 Ohm Operating Temperature 40 C to 85 C Dimensions in mm 160D006S20KXCXN0 1 5 x 1 0 x 3 25 in 38 1 x 25 4 x 82 55 mm 160D006S20KXCGN0 1 5 x 1 0 x 4 0 in 38 1 x 25 4 x 101 6 mm 160D006S20KXCGL0 1 7 x 1 4 x 2 8 in 43 18 x 35 56 x 71 12 mm 160D006S20KX16N0 1 75 x 19 0 x 2 0 ...

Страница 7: ...ODEL Former Model Name APPLICATION 160D006S20KXCXN0 Edco CX06 M Head End 160D006S20KXCGN0 w Isolated Ground Edco CX06 MI Camera End 160D006S20KXCGL0 w Isolated Ground Edco CX06 MI SBL Camera End 160D006S20KX16N0 Edco RM CX06 16R 16 Channel Coax Head End ACCESSORY PCDIN 11604KIT CX DIN Mounting Kit for 160D006S20KXCXN0 160D006S20KXCGL0 160D006S20KXC6N0 ASCO Model 160 EDCO CX and RM CX Series Surge ...

Страница 8: ... en work support 1 888 778 2733 While every precaution has been taken to ensure accuracy and completeness in this literature Schneider Electric assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or omissions ...

Отзывы: