ASCO Model 160 (EDCO CX and RM-CX Series)
Surge Protectective Device (SPD)
Introduction
The
ASCO Model 160
Surge Protective Devices (SPDs) implement three-
stage hybrid technology. The SPDs address over-voltage transients with a
primary Gas Discharge Tube (GDT) and secondary Silicon Avalanche Diode
(SAD) components. Overcurrent protection is mitigated with solid-state
resettable fuses — PTCs.
The Model 160 SPDs are designed in accordance with NFPA 780
requirements, with up to 20 kA of surge current capability. The Model 160
with Gas 14th character has an isolated ground option and is recommended
for use at the camera-end.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E, NOM-029-STPS or CSA Z462.
•
This equipment must only be installed and serviced by qualified electri
-
cal personnel.
•
Turn off all power supplying this equipment before working on or inside
equipment.
•
Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors and covers before turning on power to this
equipment.
•
This equipment must be effectively grounded per all applicable codes.
Use an equipment-grounding conductor to connect this equipment to the
power system ground.
•
Confirm that the Surge Protective Device voltage rating on the module
or nameplate label is not less than the operating voltage.
• This equipment must be installed inside an enclosure and located so,
as to prevent accidental contact with terminals during maintenance or
servicing.
• Do not place this product in service on any signal line capable of
supplying more than 150 mA continuously.
Failure to follow these instructions will result in death or serious injury.
WARNING:
This product can expose you to chemicals including
DINP, which is known to the State of California to cause cancer, and
DIDP which is known to the State of California to cause birth defects
or other reproductive harm. For more information go to: www.
P65Warnings.ca.gov.
NOTICE
LOSS OF SURGE SUPPRESSION
• Make certain that Surge Protective Device is disconnected from the
circuit it is protecting before conducting high potential insulation testing.
Failure to follow these instructions can result in equipment damage.
DANGER