25
IHT Technical Reference
Setting the Load Values
By default, the IHT allows you to set the load as a percentage of the
supply on test from 0% up to a maximum of 120%. The actual load
applied is based on the supply on test and load bank settings made on
the Setting 1-2 and Settings 2-2 Pages.
However, by pressing F3 (SELECT) you can choose between setting
the load using kVA, Power Factor or Percentage load values (If a
resistive-only load bank is used, then the selection will be percentage
load and kW only).
Power factor can be set between 0.00 and 1.00 cos
Φ
on the IHT (most
generators are rated at 0.8 cos
Φ
). However, non-unity power factor
values are dependant on the load bank capacity and the supply size.
Adjust the Load Percentage
Use the + or – keys to set the
percentage of load to be applied.
Adjust kVA
Use the + or – keys to set the kVA
value of the load to be applied.
Select Power factor
Use the + or – keys to set the
power factor of the load to be
applied.
F3
SELEC
T
F3
SELEC
T
F3
SELEC
T
Figure 1-25
Setting load values for the manual test sequence
Содержание 1251794
Страница 1: ...P N 1251794 4900 Load Bank User Manual ...
Страница 39: ...ASCO ...
Страница 40: ...ASCO ...
Страница 41: ...ASCO ...
Страница 42: ...ASCO ...
Страница 43: ...ASCO ...
Страница 44: ...ASCO ...
Страница 45: ...ASCO ...
Страница 46: ...ASCO ...
Страница 47: ...ASCO ...
Страница 48: ...ASCO ...
Страница 49: ...ASCO ...
Страница 50: ...ASCO ...
Страница 51: ...ASCO ...
Страница 52: ...ASCO ...
Страница 53: ...ASCO ...
Страница 54: ...ASCO ...
Страница 55: ...ASCO ...
Страница 56: ...ASCO ...
Страница 57: ...Intelligent Hand held Terminal IHT Technical Reference Manual ...
Страница 58: ......
Страница 63: ...IHT Technical Reference ...
Страница 95: ......
Страница 96: ...www froment co uk ...