23
Point level switch
Technical data
23
• Minimum: 80 g/l (4.99 lb/ft³)
• Depending on the density of the bulk solids adjustable in three stages: low, medium
(default), high
9.5
Installation
9.5.1
Mounting location
Orientation(→ 2, 9)
Permitted
Not permitted
Comments
Vertical from the top
Angled from the top
Cable entry must point
downwards
From the side
Cable entry must point
downwards; with protective cover
against falling solids depending
on the installation position
From the bottom (device must be
protected against shock-type
loads)
Cable entry must point
downwards
In direction of solids flow
Installation socket too long
Horizontal with shaft length
>300 mm (11.8 in)
9.5.2
Special mounting instructions
Side load on the shaft
Max. 60 N
Load on the rope
Max. 1
500 N
Operating pressure (abs.)
0.5 to 2.5 bar (7.25 to 36.3 psi)
Housing can be rotated 360 °
To adjust to the direction of the cable entries (pointing downwards)
Cable entries
The dust protection plugs which are delivered with the device are only for protection during
transport and storage. Close unused cable entry with a blind plug (IP65) when commissioning
the device.
Mechanical load of optional signal lamp
The optional signal lamp must be protected against mechanical load (impact energy > 1 J).