PART II – INSTALLATION OF TOP MOUNTING BLOCK

1

Connect FlexHead to Sprinkler System

Connect one (1) inch stainless steel flexible

hose of FLEXHEAD to one (1) inch black iron

pipe union of fire protection system in

accordance to NFPA standards, state and local

codes (Fig. 6s).

2

Connect to Top Mounting Block

A. 

Place top FLEXHEAD mounting block

onto previously installed bottom mounting

block with gasket making sure that sprinkler

head section of the FLEXHEAD unit is inserted

into two (2) inch hole in duct, and that the

four (4) stainless steel bolts of bottom

mounting block align with corresponding bolt

holes in top mounting block. Angle of flexible

hose should not exceed 90˚.

B. 

Place one (1) stainless steel washer and one

(1) stainless steel nut onto each of the four (4)

stainless steel bolts (Fig. 7s). Tighten each of

the nuts hand tight onto the block. Tightening

process of nuts onto the mounting block

should be done in a diagonal process to ensure

equal distribution of pressure throughout the

mounting block. Nuts should be tightened to

15 in. -lb. using a torque wrench. DO NOT

OVER TIGHTEN NUTS ONTO BLOCK. Installation

of FLEXHEAD is complete.