4.3 Allowable Length and Drop Height of Connecting Pipe
A
MV-Pd100W/NaB-K,
A
MV- Pd120W/NaB-K,
A
MV- Pd140W/NaB-K,
A
MV- Pd160W/NaB-
K,
A
MV-Pd140W/NaB-M,
A
MV-Pd160W/NaB-M
Allowable Value
Fitting Pipe
Total length (actual length) of fitting pipe
150m
L1+L2+L3+a+b+c+d
Length of farthest fitting
pipe (m)
Actual length
70m
L1+L2+L3+d
Equivalent length
80m
Equivalent length from the 1st manifold pipe
to farthest fitting pipe (m)
25m
L2+L3+d
Height difference
between outdoor unit
and indoor unit
Outdoor unit at
upper
30m
——
Outdoor unit at
lower
25m
——
Height difference between indoor units (m)
10m
——
Height dif
ference between indoor unit and
outdoor unit:
H
≤
30m
The 1st
branch section
Equivalent length of farthest pipe: L
≤
80m
The equivalent length of the farthest pipe from the 1st branch: L
≤
25m
The equivalent length is designed based on every 0.5m for each Y-type branch pipe
Outdoor unit
Indoor unit
Indoor unit
Height dif
ference
between indoor units:
H
≤
10m
a
d
c
b
L1
L2
L3