4 Connection of Indoor and Outdoor Unit
4.1 Manifolding Mode of Connecting Pipe
Connecting pipes for indoor unit and outdoor unit are in manifold mode. (As shown below).
Cotroller
Indoor unit
Y-Type manifold
Outdoor unit
4.2 Indoor and Outdoor Unit Capacity Code
Capacity Level
Capacity Code
Capacity Level
Capacity Code
Indoor Unit
Type 22
22
Type 56
56
Type 25
25
Type 71
71
Type 28
28
Type 80
80
Type 36
36
Type 90
90
Type 45
45
Type 112
112
Type 50
50
Type 140
140
Type 56
56
Outdoor Unit
Type 100
100
Type 120
120
Type 140
140
Type 160
160
The No. of connectable indoor units should be at least 2.
One outdoor unit can drive up to16 indoor units in maximum.
The sum of indoor unit capacity codes can be selected 50%-135% of outdoor unit capacity
code number.
Y-Type Manifold Pipe
Y-type manifold pipe can be selected from following list:
Total capacity of downstream indoor unit X
Model
Y-Type Manifold Pipe
X 200
FQ01A/A
200 X 300
FQ01B/A
300 X 700
FQ02/A