Asami AMV-Pd100W/NaB-K Скачать руководство пользователя страница 1

Thank you for choosing Commercial Air Conditioners ,please read this

owner’s manual carefully before operation and retain it for future reference.

Instruction of the 

A

MV D.C. inverter

Commercial Air Conditioners

Owner's Manual

Applicable Models :
           

A

MV-Pd100W/NaB-K 

           

A

MV-Pd120W/NaB-K 

           

A

MV-Pd140W/NaB-K 

           

A

MV-Pd140W/NaB-M 

           

A

MV-Pd160W/NaB-K 

           

A

MV-Pd160W/NaB-M 

Содержание AMV-Pd100W/NaB-K

Страница 1: ...r s manual carefully before operation and retain it for future reference Instruction of the AMV D C inverter Commercial Air Conditioners Owner s Manual Applicable Models AMV Pd100W NaB K AMV Pd120W Na...

Страница 2: ...urpose of utilizing the remaining cold air or heats in heat exchanger and also make preparations for next use This is normal When the run mode selected for indoor unit conflicts against the run mode o...

Страница 3: ...7 4 3 Allowable Length and Drop Height of Connecting Pipe 8 4 4 Dimension of Connecting Pipe 9 5 Instructions for DIP Switch 13 5 1 Set the addrss code and capacity code for indoor unit 13 6 Filling o...

Страница 4: ...reservation to prevent condensing Improper installation of pipes might cause leakage and wet the articles in the room Do not use or store flammable explosive poisonous or other dangerous substances be...

Страница 5: ...ll installation work is completed 2 2 Selection of Installation Location for Indoor Unit Avoid direct sunshine Ensure the hanger rod ceiling and building structure have sufficient strength to support...

Страница 6: ...e diameter of flexible power cable must be large enough damaged flexible power cable and connection cable must be replaced by flexible cables of such special purpose Ensure safe grounding and the grou...

Страница 7: ...Water Supply Pipe Gas Pipe Sewage Pipe Other positions that are considered to be unreliable by professionals 2 6 Noise Control Install the air conditioner unit at a well ventilated place otherwise it...

Страница 8: ...chine will not be buried under snow or subject to the influence of rubbish or oil fog To meet the noise and vibration requirements the outdoor unit shall be installed with rubber damper or spring damp...

Страница 9: ...hat can cut off the power of complete system 3 3 1 Power Cable Connection 1 Pass the cable though rubber ring 2 MV Pd100W NaB K AMV Pd120W NaB K AMV Pd140W NaB K AMV Pd160W NaB K AMV Pd140W NaB M AMV...

Страница 10: ...25 25 Type 71 71 Type 28 28 Type 80 80 Type 36 36 Type 90 90 Type 45 45 Type 112 112 Type 50 50 Type 140 140 Type 56 56 Outdoor Unit Type 100 100 Type 120 120 Type 140 140 Type 160 160 The No of conne...

Страница 11: ...from the 1st manifold pipe to farthest fitting pipe m 25m L2 L3 d Height difference between outdoor unit and indoor unit Outdoor unit at upper 30m Outdoor unit at lower 25m Height difference between i...

Страница 12: ...s selected according to the capacity of the connected downstream indoor unit The capacity of outdoor unit shall prevail if exceeded Total Capacity of Indoor Units Gas Pipe Liquid Pipe C 50 12 7 6 35 5...

Страница 13: ...kness mm Tightening Torque N m 6 35 0 5 15 30 9 52 0 7 30 40 12 7 1 45 50 15 9 1 60 65 19 05 1 70 75 Caution 1 When connecting indoor unit and pipe never pull the big and small joint of indoor unit wi...

Страница 14: ...al used on site After that wrap up the joints between the two types of materials Caution For multi split air conditioner system each pipe shall be pasted with label to identify the pipe for each syste...

Страница 15: ...rical box via cable hole Be sure to connect the indoor unit and outdoor unit in accordance with the wiring diagram labeled on the unit Refer to the electrical wiring of indoor unit and outdoor unit Th...

Страница 16: ...ired controller to assign the address The wired controller s address must be same with its corresponding indoor unit The mainboard of the wire controller has a 4 bit DIP controller to allocate the add...

Страница 17: ...er Manometer Connection hose Gas valve Liquid valve 4 After confirming that there is no leakage from the system when the compressor is not in operation charge additional R410A working fluid with speci...

Страница 18: ...unit B A C Outdoor unit D Indoor unit SN Model Indoor unit Cassette type Indoor unit Wall Mounted type Indoor unit Single Side Air Supply type Indoor unit Ducted type Liquid Pipe SN A B C D Diameter...

Страница 19: ...d water dropping Is the drainage smooth May cause condensation and water dropping Does the power supply voltage accord with the rated voltage specified on the nameplate The unit may bread down or the...

Страница 20: ...mly and correctly Inspect that whether the fan rotates in right direction Inspect that whether the valves are all openned 6 4 2 steps for running test Besides the above points test running must be ope...

Страница 21: ...COOLING Connect the system to power supply and the indoor units and the outdoor unit shall start to operate When the system is in cooling operation the low temperature and low pressure refrigerant ga...

Страница 22: ...unit to carry out heat pump heating cycle for the purpose of heating 8 Types of Indoor Units to Be Integrated Diagram of System Integration Ducted Indoor Unit Rectangular Air Outlet Single Side Air Su...

Страница 23: ...ilter may burst into flame or deform 9 1 Inspection at the Beginning of Operational Season Check the air inlet and outlet of the indoor and outdoor units to confirm there is no blockage Check the grou...

Страница 24: ...or unit is blocked Remove the obstacles Abnormal cooling or heating Air inlet or air outlet of indoor unit or outdoor unit is blocked Remove the obstacles Temperature setting is improper Adjust the se...

Страница 25: ...sensor error F3 indoor coil outlet temp sensor error F4 outdoor temp sensor error F5 inverter abnormal check error F6 low voltage error F7 outdoor defrost temp sensor error F9 exhaust temp sensor err...

Страница 26: ...ure protection of compressor E1 E1 Low pressure protection of compressor E3 E3 Exhaust temp protection of compressor E4 E4 Compressor overload protection H3 E5 Communcation error between indoor unit a...

Страница 27: ...oise is tested before outgoing The parameters below are tested under rated working condition If there is any change to them please refer to the nameplate The parameters of heating capacity of indoor u...

Страница 28: ...66129911515...

Отзывы: