18
ARZUM
the water heater, if the current plant within the building accordingly, a line
which is on the next plug socket distributer (buat) is pulled to the bath-
room. In this case the other plug sockets connected with the respective
line are canceled. The protection connected with this line should be at
40 amperes.
• IIt is necessary to use the 3x2,5 mm2 of Antigron kabel if the current
plant is not appropriate and the installment which has a standart
grounding must be connected directly to the water heater.
• If the main insurance value of your home is not enough, the main
insurance should be changed with new one which has proper value after
calculation of the electrician.
• Connection of ground and neutral line method which is called making
zero, etc. is not acceptable for grounding and never connect to this type
lines.
• It is the consumer’s responsibility to make the electricity and water
installations conformant to the appliance.
• The power connection of your electrical instant water heater mounted
onto your
installation and its operation should be undertaken by Arzum Authorized
Services.
• In the case of any failures do not open the electrical instant water heat-
er’s cover. Call the nearest
Arzum Authorized Service.
HOW TO USE THE INSTANT WATER
HEATER
• Before using your appliance check the power and
water connections.
• Switch on the input tap and wait for reservoir to be
filled with water.
• When water starts to drip it means that the reservoir
has fully filled. You can now adjust the step switches in
accordance with the temperature you like.
• Do not reduce the input water of your appliance too much.
• When switching off the appliance, bring the water
temperature selection switch to the position “0”.
• Wait until hot water is over.
• When cold water starts to drip, switch off the tap.
This process will help