II. UPS INSTALLATION
2.1
Introduction
WARNING!!!
Do not apply electrical power to the UPS equipment before the arrival of authorized service personnel.
The UPS equipment should be installed only by qualified service personnel.
The connection of the batteries and the maintenance should be done by qualified service personnel.
Do not make any short- circuit to the battery poles. Because of high voltage and high short-circuit
current, there is risk of electrical shock or burn.
Eye protection should be worn to prevent injury from accidental electrical arcs. Remove rings, watches
and all metal objects. Only use tools with insulated handles. Wear rubber gloves.
This chapter contains location installation information of the UPS and the batteries. All the establishments
have their own specialties and needs. So in this part, the installation procedure is not being explained step
by step. Instead, general procedure and the applications are explained for the technical personnel.
2.2 Unpacking
The UPS is packed and enclosed in a structural cardboard carton to protect it from damage.
1) Inspect for damage that may have occurred during the shipment If any damage is noted, call the
shipper immediately and retain the shipping carton and the UPS.
2) Carefully open the carton and take the UPS out.
3) Retain the carton and packing material for future use.
Unit package contents:
1) A user manual and Guarantee certificate.
2) Battery cabinet and/or shelf (Optional)
3) Battery connection cables.
2.3 Equipment Positioning
1.
The equipment’s installation place must be an easy serving place.
2.
Install the UPS in a protected area with adequate air flow and free of excessive dust.
3.
You must therefore allow for a minimum gap of 250 mm behind the unit to allow adequate air flow
4.
Select a suitable place (temperature between 0
C and 40
C) and the relative humidity (%90 max)
5.
It is recommended to place the equipment in an air-conditioned the room (24
C)
6.
Temperature is a major factor in determining the battery life and capacity. Keep batteries away from
main heat sources or main air inlets etc.
7.
In case of an operating the UPS in a dusty place, clean the air with a suitable air filtration system.
8.
Keep out of your equipment from explosive and flammable items.
9.
Avoid direct sunlight, rain, and high humidity.
WARNING!!!
Check the capacity of the forklift if it is available for lifting.
DO NOT LEAN OR LIFT THE UPS CABINET AFTER THE BATTERIES HAVE BEEN
INSTALLED.
2.4 Connecting the UPS Power Cables
WARNING!!!
A separate power line should be used to supply the UPS AC input. Never use the same
line to supply another electrical device. Do not use any additional cable to increase the length of the
UPS’s input cable. It is advised to use an MCCB suitable for the input current on the UPS’s input line.
Содержание ARTon Plus series
Страница 1: ...SERVICE TRAINING NOTES ARTon Plus SER S UPS 10 15 20 30 40 kVA 3 Faz Giri 3 Faz k...
Страница 2: ......
Страница 13: ...9 Figure 1 4 2 IGBT Rectifier...
Страница 14: ...10 Figure 1 4 3 Transformerless 3 Phase Inverter...
Страница 15: ...11 Figure 1 4 4 ARTonPlus series UPS Basic Diagram...
Страница 21: ...17 Figure 1 5 3 PFC3P R1 Board...
Страница 23: ...19 Figure 1 5 4 IPMD3P Board...
Страница 28: ...24 Figure 1 5 5 P3MC R5 Board...
Страница 31: ...27 Figure 1 5 6 ADVS01 R1 Board...
Страница 33: ...29 Figure 1 5 7 SDXC300 R1 Board...
Страница 36: ...32 Figure 1 5 9 ITF3 R2 Board...
Страница 39: ...35 Figure 1 5 11 OPS3 Board...
Страница 40: ...36...
Страница 41: ...37...
Страница 42: ...38...
Страница 48: ...44 K3 K1 K2 K2 Figure 2 3 ARTonPlus series 10 15 20 KVA Internal Battery Connections 2x30 60x12V 7Ah...
Страница 73: ......
Страница 74: ...1 AGKK7080 01 2008...