background image

Rail-PSU-D4 User Guide

Overview

 

Page 4 

DALI Connections

The Rail-PSU-D4 can be added to the DALI 

circuit at any point (assuming the system has 

been configured to the DALI specification).
The Rail-PSU-D4 can be put inline or joined 

to the DALI circuit (see the diagrams on the 

following page).

Either connector can be used for input or loop. 

The connections are polarity-independent.  

In a

  DALI  system,  each  circuit  (of  up  to  64 

ballasts)  must  have  a  DALI  Bus  PSU  to 

provide the voltage on the line. 

Rail-PSU-D4  is  a  DALI  Bus  PSU  with  four 

outputs (enabling it to power four DALI circuits). 
It has two connections per output to facilitate 

daisy  chain  connection,  providing  easy 

installation into new or existing DALI systems. 

Each output has a separate indicator LED 

that indicates data transmit/receive and short 

conditions.

Rail-PSU-D4 requires a 24 VDC power supply 

(available for separate purchase). 
Rail-PSU-D4  complements  the  Artistic 

Licence product Rail-DMX-DALI, which allows 

a DMX controller to command DALI ballasts.

Summary of Key Features

 

y

Four  16V,  250mA  current-limited  DALI 

compliant power bus outputs

 

y

Short-circuit proof outputs

 

y

Outputs can be stacked to make one 

16V, 1A current-limited power bus

 

y

Each output has two sets of connectors 

to facilitate daisy chain connection

 

y

LED indicators show presence of DALI 

activity,  24V  input  supply  voltage  and 

DALI bus voltage

 

y

Fully  accessible  screw  terminals  for 

easy connection

 

y

DIN Rail or surface mount 

 

y

All  outputs  align  with  Rail-DMX-DALI 

terminals

 

y

Rail-DMX-DALI  and  Rail-PSU-D4  can 

be powered together by the same 24V 

PSU

Power 

Rail-PSU-D4  must  be  powered  from 

an  external  24  VDC  power  supply.  It  is 

recommended that a ferrite core be fitted onto 

the DC power lines as close as possible to the 

Rail-PSU-D4. This protects the unit from any 

electrical spikes that appear on the DC line.

There are two power connections, either of 

which can be used as input or loop. The loop 

connection can be used to power additional 

units  or  a  Rail-DMX-DALI  (subject  to  PSU 

current rating).  

DALI was primarily designed for commercial 

lighting to respond to the growing demands 

of  energy  efficient  lighting  systems.  It  was 

DALI background

developed to provide two-way communication 

between controller and ballasts.

The most common DALI device is a 

fluorescent  ballast.  Compared  to  DMX512, 

speed  has  been  sacrificed  in  favour  of 

flexibility and ease of use.
Each DALI circuit must have a DALI Bus PSU 

(such as Rail-PSU-D4 to provide the voltage 

on the line). There can be no more than 64 

ballasts on a single bus (this corresponds 

to  one  circuit).  Ballasts    being  used  for  the 

first time require commissioning to give them 

a unique short address. A tool such as the 

Artistic Licence Dali-Scope can be used for 

this.

For  more  information  about  DALI,  please  

refer to 

www.DALI-ag.org

. A handy guide to 

DALI for those more familiar with DMX can be 

downloaded  from 

www.ArtisticLicence.com

Содержание Rail-PSU-D4

Страница 1: ...Artistic Licence Rail PSU D4 User Guide Rail PSU D4 User Guide Version 1 7...

Страница 2: ...nside the outer case of this product Always disconnect from the power supply when not in use Any specific IP rating where appropriate is given in the instructions Unless otherwise stated this product...

Страница 3: ...circuit 4 Power connection DC power input 5 Power connection DC power loop 6 DALI bus connection Circuit 1 7 DALI bus connection Circuit 1 8 DALI bus connection Circuit 2 9 DALI bus connection Circui...

Страница 4: ...nd DALI bus voltage y y Fully accessible screw terminals for easy connection y y DIN Rail or surface mount y y All outputs align with Rail DMX DALI terminals y y Rail DMX DALI and Rail PSU D4 can be p...

Страница 5: ...condition on DALI bus voltage DALI 1 4 Static Short circuit on the output Flashing Data is being transmitted LED Indication Application Diagram The diagram below shows how Rail PSU D4 could be utilise...

Страница 6: ...oHS y y Warranty 2 year return to base Power Electrical y y Input voltage 24 VDC y y Input loop connector 2 pin pluggable screw terminal 2 no y y Input power max 25 W y y Duty cycle 80 25 C y y DC fus...

Страница 7: ...me and will happily recycle any of our products that you at your expense return to us Warranty All products are covered from date of purchase by a two year return to base warranty By return to base we...

Страница 8: ...cifications are subject to change without notice Artistic Licence The Mould Making Workshop Soby Mews Bovey Tracey TQ13 9JG United Kingdom Telephone 44 0 20 8863 4515 Email Sales ArtisticLicence com W...

Отзывы: