10. Troubleshooting
Troubles
Possible Causes
Suggested Remedies
1.Unit does not start when pres-
sing on/off button.
- Water full indicator lamp blinks,
and water tank is full.
Dump the water out of the water
tank.
- Room temperature is lower
than the setting temperature.
Reset the temperature.
2. Not cool enough.
- The doors or airows are not
closed.
Make sure all the airows and
doors are closed.
- There are heat sources inside
the room.
Remove the heat sources if
possible.
- Exhaust air hose is not connec-
ted or blocked.
Connect or clean the exhaust air
hose.
- Temperature setting is too high.
Reset the temperature.
- Air inlet is blocked.
Clean the air inlet.
3. Noisy.
- The ground is not level or not
flat enough.
Place the unit on a flat, level
ground if possible.
- The sound comes from the
flowing of the refrigerant inside
the air conditioner.
It is normal.
4. E0 Code.
Room temperature sensor failed.
Replace room temperature
sensor (the unit can also work
without replacement).
5. E1 Code.
Condenser temperature sensor
failed.
Replace condenser temperature
sensor.
6. E2 Code.
Water tank full when cooling.
Take off rubber stopper and
empty the water.
7. E3 Code.
Evaporator temperature sensor
failed.
Replace evaporator temperature
sensor.
8. UV light does not activate.
UV light does not work.
Replace the lamp. Send an email
to [email protected].
Note:
The real products may look different.