OPERATION
5.5 Adjustable parameters
Parameter
Selection or parameter range
Default setting
Unit
Metric or imperial
metric
Operating
mode:
Measuring mode or control mode
measuring mode
Parameter
Differential pressure ΔP [Pa] or [InH
2
O]
Volume flow V [m
3
/h or cfm]
differential
pressure ΔP [Pa]
K-factor:
Volume flow calculation according to: V = k · √Δp
with: V = Volume flow in
[
m
3
/h
]
or
[
cfm
]
k = flow factor, adjustment range: 1...10,000
Δp = differential pressure in [
Pa
]
or
[
InH
2
O
]
Volume flow range up to 999,999 m
3
/h
Maximum volume flow (V
max
)
Measuring range: 50 Pa, k=10,000 V
max
= 70,710 m
3
/h;
Measuring range: 500 Pa, k=10,000 V
max
= 223,607 m
3
/h;
Measuring range: 1000 Pa, k=10,000 V
max
= 316,228 m
3
/h;
Measuring range: 2000 Pa, k=10,000 V
max
= 447,214 m
3
/h;
Measuring range: 4000 Pa, k=10,000 V
max
= 632,456 m
3
/h;
Measuring range: 6000 Pa, k=10,000 V
max
= 774,597 m
3
/h
K = 70
Limit values:
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 0.5 % up to 100 % of measuring range, k-factor is
considered.
OFF
Nominal
values
(setpoints):
Differential pressure from 0 % up to 100 % of measuring range.
Volume flow from 0.5 % up to 100 % of measuring range, k-factor is
considered.
placeholder
1: 8888
2: 8888
Output
voltage:
0…10 V DC
U
out
= 10 V DC
P-gain:
0...1000
P = 50
I-gain:
0…100
I = 3.15
Control
characteri-
stic:
positive/(heating):
Control deviation = set value – actual value
The output increases when: Set value > actual value
negative/(cooling):
Control deviation = actual value – set value
The output increases when: Actual value > set value
positive / heating
If selected parameter = volume flow
than follows the additional input for the k-factor
fan k-factor
k = 70
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item