11
Doc.-no.: DPC200-AC_01_EN
Issue: 07/2019
OPERATION
5.4 Control mode
Display
Action
ΔP Measurement
200 Pa
Start menu:
Press button T1 approx. two seconds
menu
Press button T2 to get to the next menu item
unit metric
Press button T1 to switch between:
metric <=> imperial
Press button T2 to get to the next menu item
operating mode
control mode
Press button T1 to switch between:
measuring mode <=> control mode
Press button T2 to get to the next menu item
parameter
diff. pressure
Press button T1 to switch between:
diff. pressure <=> volume flow
Press button T2 to get to the next menu item
If selected parameter = diff. pressure
resp. after the input of the k-factor follows:
setpoint 1
50 Pa
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
setpoint 2
250 Pa
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
output voltage
U = 10,0 V DC
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
P - parameter
50
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
l - parameter
3,15
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
controlling mode
positive / heating
Press button T1 to switch between:
positive / heating <=> negative / cooling
Press button T2 to go to the next menu
back and confirm
Press button T1 to leave the menu
Press button T2 to stay in the menu