For proper functioning and a good temperature 
distribution, the pellet insert shoul be positioned in 
a location where it is able to take in the air necessary 
for combustion of the pellet (about 40 m³/h 
must be available), as laid down in the standard 
governing the installation and in accordance with 
local national standards. The volume of the room 
must not be less than 20 m³. It is compulsory to 
install an adequate outdoor air intake which would 
allow oxidising air input necessary for correct 
operation of the product. The air flow between 
the outside and the installation premises can take 
place directly, through an opening on an external 
wall of the premises (preferred solution, see Figure 
1a); or indirectly, through air intake from the 
adjoining premises with air intake and permanently 
communicating with the installation premises (see 
Figure 1b). Adjoining premises excludes those 
used as bedrooms, bathrooms, garages, common 
areas of a building and, in general, premises in 
danger of catching fire. Consider the doors and 
windows present which could interfere with 
correct air flow to the pellet insert and maintain 
1.5 metres from any smoke outlet. The air intake 
must have a minimum total net surface of 100 cm

2

 

protected by an external grate which must not be 
obstructed and/or blocked and which should be 
periodically cleaned: the aforementioned surface 
should be increased as a result if there are other 
active generators inside the premises (for example: 
electric fans for stale air extraction, kitchen hood, 
other pellet inserts, etc...), which could generate 
a negative pressure environment. A check is 
necessary, with all the equipment on, that the drop 
in pressure between the room and the outdoors 
does not exceed a value of 4 Pa.

You can connect the air necessary for combustion 
directly to the external air intake, with a tube of at 
least 40mm, with a maximum length of 2 linear 
metres; each curve of the tube is equal to a loss of 
one linear metre.

In the presence of wood floors, 

install a floor protection surface 

in compliance with the rules in 

force in the country

FIGURA A- DIRETTAMENTE DALL’ESTERNO

FIGURA B- PER VIA INDIRETTA  DAL LOCALE ADIACENTE

FIGURE 1a- DIRECTLY FROM OUTSIDE

FIGURE 1b- INDIRECTLY FROM ADJACENT PREMISES

The pellet insert may not be 

installed in bedrooms, bathrooms 

and where another heating 

appliance without an independent air 

supply (pellet insert, pellet insert, etc.) is 

already installed. It is forbidden to install 

the pellet insert in rooms with an explosive 

atmosphere. The floor of the room in which 

the pellet insert is to be installed must be 

dimensioned appropriately to support the 

weight of the fireplace insert. Maintain 

a minimum distance of 50 mm between 

cladding and chimney insert. In the case 

of flammable walls in the vicinity of the 

chimney keep a minimum distance of (A) 

450 mm, rear (B) 300 mm, side (C) 400 mm, 

front (D) 1000 mm and floor (E) 450 mm. 

If there are particularly delicate objects 

(furniture, curtains, sofas), the distance of 

the insert must be increased considerably. 

The two side walls of the pellet insert must 

be accessible for maintenance by authorised 

technicians.

B

300

mm

A

450

mm

D

1000

mm

E

450

mm

min.

100 

cm

2

C

400

mm

Содержание NCA115-2A

Страница 1: ...d The wall where the product will be placed must not be constructed in wood or in any case made of an inflammable material and in addition it is necessary to maintain a safety distance While the pelle...

Страница 2: ...contact the dealer or the Authorized Assistance Center The pellet pellet insert must only be operated in living environments This pellet insert being controlled by an electronic board permits a comple...

Страница 3: ...ould be used only for the intended purpose Any other use is considered improper and therefore dangerous Do not put in the hopper other than wood pellets When the pellet insert is operating the surface...

Страница 4: ...4 of 36 EN Never turn off the heater by removing electricity Let always complete the shutdown cycle otherwise you may damage the structure and have trouble lighting in the future...

Страница 5: ...ery hot Do not touch them except with the appropriate protection The plug of the device power cable must be connected only after installation and assembly of the device and must remain accessible afte...

Страница 6: ...ale air extraction kitchen hood other pellet inserts etc which could generate a negative pressure environment A check is necessary with all the equipment on that the drop in pressure between the room...

Страница 7: ...let is not provided increase the air inlet section to 340 cm2 The air flow entering from below must not be obstructed by the base or other elements placed inside the installation niche The air flow mu...

Страница 8: ...draught and the soot could catch fire Have a professional chimney sweep clean the flue and the chimney at least once a year and before switching on the generator after periods of inactivity Lack of c...

Страница 9: ...and the plug of the power lead to the power supply Push the ON button in the back of the stove Lie the stove on the gauge with caution and push it in the chimney until it reaches its correct position...

Страница 10: ...heat you are advised to use at least a T250 Keep a distance from flammable and or combustible objects at least 50 cm and from curtains and furniture The pellets are cylinders of compressed wood produc...

Страница 11: ...automatically enter the starting phase Press keys 1 and 2 to adjust temperature and use keys 6 and 5 to adjust operating power To turn off the pellet insert hold down key To replace the 3 volt battery...

Страница 12: ...the pellet insert the positions of the tubes in the rear view are indicative and tolerance of 10 mm measures with a tolerance of about 10 mm 691 4 57 27 579 279 583 51 5 639 531 691 480 579 279 583 5...

Страница 13: ...rt the positions of the tubes in the rear view are indicative and tolerance of 10 mm measures with a tolerance of about 10 mm 711 315 581 5 55 5 637 580 218 6 55 8 O 8 0 195 660 218 6 339 5 57 O 4 5 3...

Страница 14: ...e 13 O2 mg m3 130 120 CO concentration at reduced reference 13 O2 mg m3 229 229 Nominal efficiency 88 8 88 3 Reduced efficiency 90 90 Average consumption Kg h 1 24 2 63 1 24 2 99 Heatable surface mc 2...

Страница 15: ...read START START The led resistance is switched on After 1 minute the display will read LOAD PELLET LOAD PELLET the pellet insert will load the pellets and continue lighting the resistor Once the app...

Страница 16: ...package Pict 10 Using a screwdriver remove the supporting bracket from the display holder on the back Pict 11 12 Fasten the supporting bracket to the wall using 2 screws the fastening system must sui...

Страница 17: ...ndicators Chronothermostat This signalises that the automatic single or daily switching on or off of the pellet insert is on The automatic programming can be set only using the remote control Resistan...

Страница 18: ...mokes extractor and gear motor are on CADENCE CLEANING The pellet insert is cleaning the brazier The smokes ex tractor is working at its max speed and the pellets loading is minimal WORK The pellet in...

Страница 19: ...1 and 2 select whether or not to activate the thermostat on off which allows you to program the automatic ignition of the pellet insert Once the thermostat is activated deactivated press button 4 OFF...

Страница 20: ...prog 2 on off 16 thursday prog 2 on off 17 friday prog 2 on off 18 saturday prog 2 on off 19 sunday prog 2 on off 20 start program 3 hour 21 stop program 3 hour 22 monday progr 3 on off 23 tuesday pr...

Страница 21: ...mostat It s possible to set two operating ranges delimited by the times set according to the following table where the OFF setting tells the clock to ignore the command The weekly programmer has 4 ind...

Страница 22: ...the menu Select the desired language using the keys 1 e 2 08 30 M 3 4 03 STop 1 week end menu level input dialogue PROGRAMME 1 menu level selection meaning possible values 02 03 02 START PROGRAM 1 ac...

Страница 23: ...access it STAND BY function is set by default to OFF To activate this feature press 1 on the display you will see STAN BY MODE ON Press SET 3 to con firm and then OFF 4 to leave The STAND BY mode is n...

Страница 24: ...o high Switch off the Pellet insert allow it to cool down and perform ordinary cleaning If the problem persists contact an Authorized Assistance Center for cleaning the Pellet insert and the flue ALAR...

Страница 25: ...ok at the one end of the detail 1 in the hole of the handle and pull the door 1 Pict 7 opening door Cleaning the brazier and brazier support When the flame assumes a red colour or seems weak and is ac...

Страница 26: ...et insert is switched off and cold start up the scrapers of the pipe for heat exchange 5 6 times You need to pull and push the two control levers set between the front grids through which the air flow...

Страница 27: ...the metal parts of the pellet insert use a soft cloth dampened with water Never clean the metal parts with alcohol thinners petrol acetone or other degreasing substances If such substances are used o...

Страница 28: ...s Installa the pellet insert again Place it on the support and push it slowly until it reaches the apposite check pin Check that the flue system lies perfectly in the T pipe Pict 15 how to remove the...

Страница 29: ...performance It is therefore necessary to clean the fans at least once a year Since said operation requires dismantling several parts of the pellet insert have the fans cleaned only by our Technical A...

Страница 30: ...onic board sends a warning signal and the display will show SERVICE SERVICE This indicates the need for a thorough cleaning of the pellet insert by a CAT The lack of such cleaning could result in fail...

Страница 31: ...r shuts the pellet insert when the flue gas temperature drops below the preset value Electrical safety the pellet insert is protected against violent surges of current ex lightnings by the main fuse 4...

Страница 32: ...32 of 36 EN...

Страница 33: ...d defective 1 Check that the power cord is connected 2 Use the switch back to operate it 3 Unplug the pellet insert from the power outlet for about one minute and then turn on If the problem persists...

Страница 34: ...er ashtray 10 Perform periodic cleaning 11 Check the operation of the extractor flue 12 Contact an authorized service center 13 Make sure the place of stowage pellet and replace it with a handful of d...

Страница 35: ...se the level in the param eter relative to the speed of the fan exhaust fumes Contact your Authorized Service Center 7 Check the quality of the pellets Contact your Authorized Service Center 8 Increas...

Страница 36: ...Change the type of pellet recommended by the manufacturer Sometimes depending on the type the stage of adjustment of the parameters need to vary the level relating to the loading of pellets 9 Increas...

Страница 37: ...ine can only take place following the unquestionable decision by the manufacturer in special cases 3 The Company declares no responsibility for any damage that may directly or indirectly result in per...

Страница 38: ...38 of 36 EN NOTES...

Страница 39: ...39 of 36 EN NOTES Cod 001247 Date 08 2021...

Отзывы: