66
S
YSTEM DESCRIPTION
Table 1: Fault List
LCD Symbol In
Part A
Description
Solution Advice
The UPS is over- loaded
Check load level display and remove some load
The UPS is over temperature
1. Ensure the ambient temperature is below 40°C
2. Turn off the UPS and wait for a while to make it
cooling
The UPS output is short-
circuit
1. Disconnect all loads and ensure nothing is
lodged in output receptacles
2. Ensure loads are not detective or shorted
internally
Fan fails
Please contact your local dealer for fan checking or
exchanging
output voltage is out of
range(inverter fails)
Please contact your local dealer
UPS internal fault
Please contact your local dealer
Table 2
Battery level
0%~20%
20%~40%
40%~60%
60%~80%
80%~100%
Tab. 3
Load level
0~5%
5~25%
25%~50%
50%~75%
75%~102%
flashing
>102%
After overloading, the UPS powers the loads and a hurried alarm will sound (1s on/1s off). By reducing the load
within the 100% threshold, the UPS returns to normal operating mode.
When the overload level is too high, the overload protection is activated and the UPS will be completely
shutdown.
To restore normal operation following failure due to overloading (continuous beep and load not powered), reduce
the load so that it falls within the 100% threshold. Hold the OFF button down until the continuous beep stops and
then release it. Wait until the UPS is completely shutdown and then switch on again.
Содержание Spring 500-3000VA
Страница 2: ......
Страница 15: ...53 REAR VIEW Spring 500 800 1100 T Spring 1500 2000 T Spring 500 800 1100 R Spring 1500 RT...