background image

adjusted for the 10 unit grid

 

INFUSIONS

®

 

Accent Canopies

Assembly and  Installation Instructions

1. PRODUCT DESCRIPTION 

Infusions

®

 Accent Canopies are available in three sizes  

(2' x 5', 2' x 6', and 4' x 10') and a wide variety of translucent 
and aluminum finishes. 2' x 5' and 2' x 6' canopies can be 
installed as hills or valleys with either 60º or 90º arcs. 4' x 10' 
canopy hill or valley arcs can be either 30º or 50º. 

 Infusions Canopies can be suspended individually or linked 
together in a variety of ways, including side-to-side and  
end-to-end. They may be suspended from the building 
structure or one end may be attached to a wall.

2. DESIGN AND INSTALLATION LIMITATIONS 

Infusions panels should always be installed in accordance 
with all applicable building codes and regulations.

Do not cut holes in or drill through Infusions panels. Doing so 
may cause the panel to bend in an irregular fashion. 

Do not allow panel to get wet.

Panels are susceptible to “wicking.” If the panel is placed 

in a damp or wet area, water may “wick” up through the 

panel.

The lowest point of a suspended Infusions panel 
should be at least 7'-6" above the finished floor 
surface.

Canopies must be suspended with the extrusions 

level and the tension cables no more than 30° off horizontal.

Infusions panels are not approved for exterior application.

Polycarbonate panels can be damaged by exposure to high 
temperatures. Panel temperature should not be permitted to 
exceed 100º F after the tensioning cables have been installed. 
Follow these guidelines for minimum distance from standard 
light sources: 
 
 
 
 
 
 
 
 

Lamp Type 

Label Wattage

Minimum Distance

Halogen FL XL 
PAR 30

60

14"

Incandescent Bulb

120

15"

Quartz Halogen 
Work Light

500

23"

3. FIRE PERFORMANCE

Infusions Canopies, as with other architectural features 
located at the ceiling, may obstruct or skew the planned 
fire sprinkler water distribution pattern or possibly delay or 
accelerate the activation of the sprinkler or fire detection 
systems by channeling heat from a fire either toward or 
away from the device. Designers and installers are advised 
to consult a fire protection engineer, NFPA 13, and their 
local codes for guidance where automatic fire detection and 
suppression systems are present.

IMPORTANT:

 For proper fire performance, do not install 

polycarbonate panels so that any portion of the panel is 
suspended directly above any portion of an aluminum panel.

Infusions Canopies have been tested according to NFPA 286 
and are equivalent to Class A Interior Finish as defined in 
Chapter 8 of the International Building Code. 

Metal panels are non-combustible.

Contact TechLine customer support at 1 (877) 276-7876 for 
specific US and Canadian fire performance data.

4. PANEL KIT CONTENTS

Infusions Canopy Panel Kit 

Kit Contents: 
 

• Flat Infusions Panel (1 or 2) with extrusions attached 

 

• Cables to form arcs 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
  

NOTE:

 Panel extrusions for nominal 4' x 10' panels are 48-1/2" 

long. Suspension points for those panels are 44-1/2" apart.

Basic Canopy Kit A

_30°

<

Tension Cable Length

Arc 

2' x 5'

2' x 6'

60°

58"

69-3/4"

90°

55"

65-3/4"

Arc

4' x 10'

30°

120"

50°

117-3/10"

Содержание INFUSIONS Accent Canopies Series

Страница 1: ...after the tensioning cables have been installed Follow these guidelines for minimum distance from standard light sources Lamp Type Label Wattage Minimum Distance Halogen FL XL PAR 30 60 14 Incandescen...

Страница 2: ...required for this operation with larger panels CAUTION Only use cables from Panel Kits for tensioning panels Cables from Kit 7004 7005 and 7010 shown in section 6 are only for hanging panels Hill and...

Страница 3: ...Gripper Anchor Cap Bottom End Cable Adjuster Gripper Bottom End Assembly 4 Insert Top Cable into Bottom End Cable Adjuster and thread cable thru opening NOTE Gripper Structure Anchors have 1 4 20NC i...

Страница 4: ...rmit attaching rows of end linked canopies side to side with either no space between them a 1 2 of space or a space of 3 11 1 Use the Dual Canopy Hanging Kit item 7041 at linked canopy ends A dual ass...

Страница 5: ...e the same process for all hinge assemblies The end of the Hinge Rod will always be flush with an extrusion 11 5 Use this hardware the Dual Hinge Flush Linking Kit item 7045 to join paired canopies en...

Страница 6: ...th offsetting 4 x 10 panels below WARNING Do not attempt to remove the tension cable from a canopy that is suspended Doing so may cause serious bodily injury Large Extrusion Small Extrusions Shown in...

Страница 7: ...will generate the greatest amount of pendulum reaction during a seismic event and should therefore be avoided When it is not practical to use cables greater than 20 long allow lateral clearance aroun...

Страница 8: ...ation and many other technical services call TechLine customer support at 1 877 276 7876 or FAX 1 800 572 TECH For the latest product selection and specification data visit armstrongceilings com infus...

Отзывы: