installation &
operating instructions
Design Envelope
4300
&
4380
Vertical In-line Pumping Unit
16
3.0 networking controls
Setup of
bas
protocol, Node address, baud rate, and for
ip
setup
3.1 modbus ip & rtu
modbus address value range
description
10 0 0 5
1
= Hand mode
Pump in Hand mode
10 0 0 6
1
= off
Pump is off
10 0 07
1
= auto
Pump is in automatic mode
10 0 3 5
0
= stopped,
1
= running
Run feedback
10 0 69
0
= ok,
1
= alarm
Pump alarm
10 079
0
= ok,
1
= alarm
Run feedback alarm
10 0 8 9
0
= ok,
1
= alarm
Pump drive fault
152
Set pump to hand mode
153
Set pump to off
154
Set pump to auto mode
3 0 0 41
0 -10 0 0 (0 % -10 0 %)
Pump speed
3 0 0 54
0 -10 0 0 0 (0 -10 0 0 .0)
amps
Pump drive current
3 0 0 55
0 -10 0 0 0 (0 -10 0 0 .0)
VAC
Pump drive AC voltage
3 0 0 5 6
0 -10 0 0 0 (0 -10 0 0 .0)
kW
Pump drive power
3 0 0 57
0 -10 0 0 (0 .0 -10 0 . 0) %
Pump drive speed feedback
3 0 0 94
0 -32767 (0 . 0 -3276 .7)
Pump head
4 013 9
0 -10 0 0 (0 .0 -10 0 . 0) %
Pump hand speed
4 0151
0 - 9 9 9 9 (0 . 0 - 9 9 9.9)
Design head
4 0152
0 - 9 9 9 9 (0 . 0 - 9 9 9.9)
Zero flow head
3 5 0 0 5
0 -32767
Pump flow
3 5 016
0 - 9 9 9
hours
Pump operating run hours
3 5 017
0 -32 0 0 0
hours
* 10 0 0
Pump operating run Khours
4 5 0 52
0 -32767 (0 -327670)
Flow design