8.0 fuse and wire recommendation
Armstrong recommends
ul 248-12
Listed Class
rk1
current-
limiting and Fast-acting fuses for upstream protection of instal-
lations within the
nec/ul
jurisdiction.
Example fuses suitable for upstream protection are detailed
below. The Bussmann
ktr-r (200v)
and the
kts-r (400v)
fuses are class
rk1
and
csa
certified to
c22.2
No.
248.12
Bussmann
ktx-r
fuses offer
200
kA (
vac rms
) interrupting
rating.
suitable fuses - iecm
drive rating
[kW]
200 v class
drive
400 v class
drive
0 .75
ktn-r-10
kts-r-6
1 .1
ktn-r-10
kts-r-6
1 . 5
ktn-r-15
kts-r-10
2. 2
ktn-r-20
kts-r-10
3 .0
ktn-r-25
kts-r-15
3 .7
ktn-r-30
—
4 .0
ktn-r-30
kts-r-20
5.5
ktn-r-50
kts-r-25
7.5
ktn-r-60
kts-r-30
All cabling must comply with national and local regulations on
cable cross-sections and ambient temperature.