background image

Page 3 of 4

AQUASTAT CONTROL ACCESSORY

TECHNICAL DATA

Description:

Aquastat (thermostatic) switch 

Type: 

Surface sensing, snap acting bimetallic disc

Enclosure: Environmentally 

sealed

Switch Modes*:

105 ± 5°F (40 ± 2°C) pump switches OFF
85 ± 6°F (29 ± 3°C) pump switches ON

Contact Position: Normally open
Mounting:

1/2": Clip-on type for 5/8" O.D. system piping size (i.e., 1/2" I.D. copper tubing or 3/8" steel pipe)
3/4": Clip-on type for 7/8" O.D. system piping size (i.e., 3/4" I.D. copper tubing or 1/2" steel pipe)
May be mounted on either the inlet or outlet piping of the circulator.

Lead Length:

14” (356 mm)

*Temperatures indicated are at pipe surface

AQUASTAT INSTALLATION

1.

Follow Steps 1, 2 and 3 in the Timer Installation section 

2.

The aquastat control is a surface temperature sensing device that must be in contact 
with the system piping to operate properly. Separate models include clip-on mounts 
for 3/4" (7/8" O.D.) and 1/2" (5/8" O.D.) copper tubing. (See Fig. 3)

3.  Connect the black, green and white lead wires according to the wiring diagram (Fig. 4)

Note:

Lead Wiring Specification - Minimum, 6” (152 mm) long, 14 AWG, rated 
minimum 140ºF (60ºC). Provided with R/C crimp 
connectors for attachment to the ground.

4.

Close the terminal box cover and fasten the screw

TIMER and AQUASTAT INSTALLATION

Follow the installation steps in both the Timer and Aquastat installation instructions and refer to Fig. 5 for 
the wiring connections.

Fig. 4  Astro Series circulator with Aquastat Control wiring diagram

Fig. 3

Fig. 5  Astro Series circulator with 24-Hour Timer and Aquastat Control wiring diagram

Отзывы: