background image

Page 2  of 13

507296-01

Issue 1650

Improper  installation,  adjustment,  alteration,  service, 

or maintenance can cause injury or property damage. 

Refer to this manual. For assistance or additional 

information,  consult  a  qualified  installer  or  service 

agency.

WARNING

Installation

These instructions explain the recommended method of 

installation of the packaged heat pump and air conditioner 

units and associated electrical wiring.

This  unit  is  designed  and  approved  for  use  as  a  self-

contained air-to-air outdoor heat pump and air conditioner 

system.

The  units  are  factory-equipped  with  a  transformer  and 

blower  control  for  applications  without  auxiliary  heat. 

Electric heat accessory kits (PHK-) can be ordered for field 

installation of additional heat where required.

These  instructions,  and  any  instructions  packaged  with 

mating components and/or accessories, should be carefully 

read prior to beginning installation. Note particularly any 

CAUTIONS

 or 

WARNINGS

 in these instructions and all 

labels on the units.

These instructions are intended as a general guide only, 

for use by qualified personnel and do not supersede any 

national or local codes in any way. Compliance with all local, 

state, provincial, or national codes pertaining to this type of 

equipment should be determined prior to installation.

Inspection of Shipment

Upon receipt of equipment, carefully inspect it for possible 

shipping damage. If damage is found, it should be noted 

on the carrier’s freight bill. Take special care to examine 

the unit inside the carton if the carton is damaged. File a 

claim with the transportation company.

If any damages are discovered and reported to the carrier, 

DO NOT INSTALL THE UNIT, 

as claim may be denied

.

Check  the  unit rating  plate  to  confirm  specifications 

are as ordered.

Limitations

The unit should be installed in accordance with all national 

and local safety codes.

Limitations of the unit and appropriate accessories must 

also be observed.

The  unit  must  not  be  installed  with  any  ductwork  in  the 

outdoor air stream. The outdoor fan is not designed to 

operate against any additional static pressure.

Location

The unit is designed to be located outdoors with sufficient 

clearance for free entrance to the air inlet and discharge 

air  openings.  The  location  must  also  allow  for  adequate 

service access. 

The unit must be installed on a solid foundation that will 

not settle or shift. Adequate structural support must be 

provided. Install the unit in level position. Isolate the base 

from the building structure to avoid possible transmission 

of sound or vibration into the conditioned space.

The heat pump unit foundation should be raised to a 

minimum of 3” above finish grade.

 In areas that have 

prolonged  periods  of  temperature  below  freezing  and 

snowfall, the heat pump unit should be elevated above the 

average  snow  line.  Extra  precaution  should  be  taken  to 

allow free drainage of condensate from defrost cycles to 

prevent ice accumulation. The unit should not be located 

near  walkways  to  prevent  possible  icing  of  surface  from 

defrost condensate.

Avoid placing the unit near quiet areas, such as 

sleeping quarters or study rooms.

 Normal operating 

sound levels may be objectionable if the unit is placed near 

certain rooms.

For improved start-up performance, the indoor coil 

should be washed with suitable detergent to remove 

any residue from manufacturing processes. 

Roof Curb Installation

If a roof curb is used, follow the manufacturer’s Installation 

Instructions and be sure that all required clearances are 

observed. 

Rigging and Handling

Before  lifting  a  unit,  make  sure  that  the  weight  is 

distributed equally on the cables so that it will lift evenly.

CAUTION

Exercise care when moving the unit. Do not remove any 

packaging until the unit is near the place of installation. 

An optional lifting lug kit may be purchased separately for 

use in rigging the unit for lifting. Spreaders whose length 

exceeds the unit depth dimension by 6 inches MUST be 

used across the top of the unit. 

Units may also be moved or lifted with a forklift while still in 

the factory-supplied packaging. 

The lengths of the forks 

of the forklift must be a minimum of 42”.

Содержание RP14AC Series

Страница 1: ...adian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should be consulted before installation is made Such applicable regulations or requirements take precedence over the general instructions in this manual CAUTION Save these instructions for future reference INSTALLATION AND MAINTENANCE INSTRUCTION...

Страница 2: ...d with any ductwork in the outdoor air stream The outdoor fan is not designed to operate against any additional static pressure Location The unit is designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings The location must also allow for adequate service access The unit must be installed on a solid foundation that will not settle or s...

Страница 3: ...C 410A are higher than pressures in units charged with HCFC 22 All service equipment MUST be rated for use with HFC 410A refrigerant WARNING Clearances All units require certain clearances for proper operation and service Refer to Table 1 for the minimum clearances to combustibles required for construction servicing and proper unit operation In the U S units may be installed on combustible floors ...

Страница 4: ...ed so that water or moisture cannot be drawn into the unit during normal operation CAUTION Units are factory wired for a 230 volt power supply If power supply is 208 volts it will be necessary to change a wire connection on the unit transformer from 240V terminal to 208V terminal as shown on the wiring diagram Use only copper conductors If any of the original unit wiring is replaced the same size ...

Страница 5: ...achments 5 Install drain pan overflow switch and wire according to downflow conversion kit instructions Filters Air filters are not supplied with the unit A field provided air filter must always be installed ahead of the evaporator coil and must be kept clean or replaced Dirty filters will reduce the airflow of the unit An optional filter rack kit may be purchased separately for installation insid...

Страница 6: ...red for safety while servicing do not open the system disconnect switch Heater Kit Accessory if used The unit is fully equipped for cooling operation without auxiliary heat A heater kit accessory may also be used To install the heater kit accessory see Figure 6 1 Disconnect the power and open the main control access 2 Disconnect the plug separating the high voltage wire harness Remove the high vol...

Страница 7: ... send a signal to the defrost control board to start the defrost timing It also terminates defrost when the liquid line warms up to 60 F Figure 7 Defrost Control Board Diagnostic LEDs 24V Terminal Strip Connections Defrost Interval Timing Pins Low Pressure Switch optional Test Pins Compressor Delay Pins High Pressure Switch Reversing Valve Defrost Thermostat FAN K1 RELAY C2 U1 U2 K2 RELAY K3 RELAY...

Страница 8: ...he control board In addition the diagnostic LEDs will indicate a locked out pressure switch after the fifth occurrence of an open pressure switch see Table 3 The unit will remain locked out until power to the board is interrupted then re established or until the jumper is applied to the TEST pins for 0 5 seconds NOTE The defrost control board ignores input from the low pressure switch terminals as...

Страница 9: ...he system shut off all electrical power to the unit Turn off accessory heater power switch if applicable Electrical shock could cause personal injury or death WARNING Periodic inspection and maintenance normally consists of changing or cleaning the filters and cleaning the outdoor coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspect onc...

Страница 10: ...IF USED 208 230 1 60 POWER SUPPLY WITH MIN 75 C COPPER WIRE G W1 C R CONTACTOR CONTROL CIRCUIT WIRING TO BE 24 VOLT N E C CLASS 2 L1 T1 COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR DUAL CAPACITOR COMPRESSOR TRANSFORMER C S R L2 537662 01 24V LINE VOLTAGE FIELD INSTALLED WARNING ELECTRIC SHOCK HAZARD UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES S1 K1 T1 B3 B4 K1 2 C12 B1 K1 1 SEE ...

Страница 11: ...T GRN 5 7 5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK J2 1 J2 2 BLK C 1 2 3 4 5 J2 6 J2 5 WHT BLU RED YEL WHT B1 PUR B4 BLACK ORG L N G B3 S1 TRANSFORMER TI L G N BLK K1 1 CONTACTOR YEL W STRIPE CONTACTOR K1 2 BLU BLU GRN CONTACTOR KI YEL BLK J2 4 NOTE TAP1 FOR FAN ONLY TAP 2 FOR COOLING TAP3 FOR HIGH STATIC COOLING TAP4 AND TAP5 FOR ELECTRIC HEAT REFER TO HEATING LABEL BLK W STRIPE YEL THERMA...

Страница 12: ...open will not be seen when Y1 is off Instead the Normal Operation or Anti Short Cycle code will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has already expired See instructions or markings on System Diagnostic Module for codes of System Diagnostic Module ...

Страница 13: ...rt Cycle code will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has already expired W1 W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 10 15 20KW MODELS 5 7 5 KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK DEFROST CONTROL WHT DEFROST CONTROL J2 2 J2 4 B...

Отзывы: