background image

507296-01

Page 5  of 13

Issue 1650

Duct System

Duct system should be designed and sized according to the 

methods in Manual Q of the Air Conditioning Contractors of 

America (ACCA).

A closed return duct system shall be used. This shall not 

preclude use of economizers or outdoor fresh air intake. It 

is recommended that supply and return duct connections 

at the unit be made with flexible joints.

The supply and return air duct systems should be designed 

for the CFM and static requirements of the job. 

They 

should not be sized to match the dimensions of the 

duct connections on the unit. 

The  unit  is  shipped  ready  for  horizontal  flow  (side  duct 

connections). Before attaching side ducts, bend perforated 

duct tabs out to assist with duct alignment and attachment. 

Duct attachment screws are intended to go into the duct 

panel. Duct to unit connections must be sealed and 

weather proofed.

If downflow duct system is desired, a downflow conversion 

kit is required, and the following conversion is required.

1. 

Using  a  knife,  cut  following  the  marked  cut  lines  on 

the unit base insulation to access bottom metal covers 

underneath the insulation.

2.  Remove the screws securing the bottom covers and 

discard the bottom covers (supply and return).

3. 

Remove screws located between the supply and return 

openings that attach the blower deck to the base, and 

discard these screws. These screws can interfere with 

bottom duct connections or roof curb seals.

4. 

Secure  side  duct  covers  provided  in  the  downflow 

conversion  kit  over  the  side  duct  openings  (use 

dimples on back panel to locate cover attachments).

5. 

Install drain pan overflow switch and wire according to 

downflow conversion kit instructions.

Filters

Air filters are not supplied with the unit. A field-provided air 

filter must always be installed ahead of the evaporator coil 

and must be kept clean or replaced. Dirty filters will reduce 

the airflow of the unit. 

An  optional  filter  rack  kit  may  be  purchased  separately 

for installation inside the unit’s coil compartment. Air filter 

sizes are shown in Table 2 for use with filter rack kit.

The filter rack must be installed prior to installation of 

the unit in applications where access to the rear panel 

is limited.

NOTE:

Table 2. Unit Air Filter Sizes - inches

Unit Model

Filter 1

Filter 2

24,30,36

14 X 20

20 X 20

42,48,60

20 X 20

20 X 20

Condensate Drain

This  package  unit  is  equipped  with  a  3/4”  FPT  coupling 

for condensate line connection. Plumbing must conform 

to  local  codes.  Use  a  sealing  compound  on  male  pipe 

threads.

Do not 

operate unit without a drain trap. The condensate 

drain  is  on  the  negative  pressure  side  of  the  blower; 

therefore, air being pulled through the condensate line will 

prevent positive drainage without a proper trap.

The condensate drain line must be properly trapped, 

routed to a suitable drain and primed prior to unit 

commissioning.

 

NOTE

Install drain lines and trap so they do not block 

service access to the unit.

See Figure 5 for proper drain arrangement. The drain line 

must pitch to an open drain or pump to prevent clogging 

of the line.  Seal around the drain connection with suitable 

material to prevent air leakage into the return air system. 

To  prime  trap,  pour  several  quarts  of  water  into  drain, 

enough to fill drain trap and line. 

Drain lines should be hand-tightened only. Do not use 

tools to tighten fitting into drain.

CAUTION

Содержание RP14AC Series

Страница 1: ...adian Electrical Code Part 1 CSA 22 1 latest edition in Canada and any state or provincial laws or local ordinances Local authorities having jurisdiction should be consulted before installation is made Such applicable regulations or requirements take precedence over the general instructions in this manual CAUTION Save these instructions for future reference INSTALLATION AND MAINTENANCE INSTRUCTION...

Страница 2: ...d with any ductwork in the outdoor air stream The outdoor fan is not designed to operate against any additional static pressure Location The unit is designed to be located outdoors with sufficient clearance for free entrance to the air inlet and discharge air openings The location must also allow for adequate service access The unit must be installed on a solid foundation that will not settle or s...

Страница 3: ...C 410A are higher than pressures in units charged with HCFC 22 All service equipment MUST be rated for use with HFC 410A refrigerant WARNING Clearances All units require certain clearances for proper operation and service Refer to Table 1 for the minimum clearances to combustibles required for construction servicing and proper unit operation In the U S units may be installed on combustible floors ...

Страница 4: ...ed so that water or moisture cannot be drawn into the unit during normal operation CAUTION Units are factory wired for a 230 volt power supply If power supply is 208 volts it will be necessary to change a wire connection on the unit transformer from 240V terminal to 208V terminal as shown on the wiring diagram Use only copper conductors If any of the original unit wiring is replaced the same size ...

Страница 5: ...achments 5 Install drain pan overflow switch and wire according to downflow conversion kit instructions Filters Air filters are not supplied with the unit A field provided air filter must always be installed ahead of the evaporator coil and must be kept clean or replaced Dirty filters will reduce the airflow of the unit An optional filter rack kit may be purchased separately for installation insid...

Страница 6: ...red for safety while servicing do not open the system disconnect switch Heater Kit Accessory if used The unit is fully equipped for cooling operation without auxiliary heat A heater kit accessory may also be used To install the heater kit accessory see Figure 6 1 Disconnect the power and open the main control access 2 Disconnect the plug separating the high voltage wire harness Remove the high vol...

Страница 7: ... send a signal to the defrost control board to start the defrost timing It also terminates defrost when the liquid line warms up to 60 F Figure 7 Defrost Control Board Diagnostic LEDs 24V Terminal Strip Connections Defrost Interval Timing Pins Low Pressure Switch optional Test Pins Compressor Delay Pins High Pressure Switch Reversing Valve Defrost Thermostat FAN K1 RELAY C2 U1 U2 K2 RELAY K3 RELAY...

Страница 8: ...he control board In addition the diagnostic LEDs will indicate a locked out pressure switch after the fifth occurrence of an open pressure switch see Table 3 The unit will remain locked out until power to the board is interrupted then re established or until the jumper is applied to the TEST pins for 0 5 seconds NOTE The defrost control board ignores input from the low pressure switch terminals as...

Страница 9: ...he system shut off all electrical power to the unit Turn off accessory heater power switch if applicable Electrical shock could cause personal injury or death WARNING Periodic inspection and maintenance normally consists of changing or cleaning the filters and cleaning the outdoor coil On occasion other components may also require cleaning Filters Filters are not supplied with the unit Inspect onc...

Страница 10: ...IF USED 208 230 1 60 POWER SUPPLY WITH MIN 75 C COPPER WIRE G W1 C R CONTACTOR CONTROL CIRCUIT WIRING TO BE 24 VOLT N E C CLASS 2 L1 T1 COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR DUAL CAPACITOR COMPRESSOR TRANSFORMER C S R L2 537662 01 24V LINE VOLTAGE FIELD INSTALLED WARNING ELECTRIC SHOCK HAZARD UNIT MUST BE GROUNDED IN ACCORDANCE WITH NATIONAL AND LOCAL CODES S1 K1 T1 B3 B4 K1 2 C12 B1 K1 1 SEE ...

Страница 11: ...T GRN 5 7 5KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK J2 1 J2 2 BLK C 1 2 3 4 5 J2 6 J2 5 WHT BLU RED YEL WHT B1 PUR B4 BLACK ORG L N G B3 S1 TRANSFORMER TI L G N BLK K1 1 CONTACTOR YEL W STRIPE CONTACTOR K1 2 BLU BLU GRN CONTACTOR KI YEL BLK J2 4 NOTE TAP1 FOR FAN ONLY TAP 2 FOR COOLING TAP3 FOR HIGH STATIC COOLING TAP4 AND TAP5 FOR ELECTRIC HEAT REFER TO HEATING LABEL BLK W STRIPE YEL THERMA...

Страница 12: ...open will not be seen when Y1 is off Instead the Normal Operation or Anti Short Cycle code will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has already expired See instructions or markings on System Diagnostic Module for codes of System Diagnostic Module ...

Страница 13: ...rt Cycle code will be seen Also when a pressure switch opens and caused a short cycle lockout the pressure switch open code will be seen until it closes then the short cycle lockout code will flash unless it has already expired W1 W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 10 15 20KW MODELS 5 7 5 KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK DEFROST CONTROL WHT DEFROST CONTROL J2 2 J2 4 B...

Отзывы: