Heat Pump Operation (Heating and Cooling)
Figure 23.
Room thermostat
calls for first
stage?
Air Handler Control (AHC) receives inputs on Y1 terminal
.
Y1 terminal on air handler control is configured as input and
passes signal from room thermostat to outdoor unit.
Y1 input to the air handler control will control the indoor
blower according to the cooling or heating mode blower
speed, ramping and adjust selection jumper pins.
Air Handler Control (AHC) receives inputs on Y1 and O
terminals
.
Y1 terminal on air handler control is configured as input and
passes signal from room thermostat to outdoor unit.
Y1 input to the air handler control. Will control the indoor
blower according to the cooling mode blower speed, ramping
and adjust selection jumper pins.
Room thermostat calls for
second stage?
Still calling for first
stage?
Y2 terminal on air
handler control is
configured as input and
passes signal from room
thermostat to outdoor
unit.
Y2 terminal is an
input to the air
handler control. The
indoor blower will be
controlled according
to the jumper pin
selections.
Still calling for second
stage?
De-energize Y2 terminal on air handler
control. Indoor blower speed will reset to
Y1 demand.
De-energize Y1 (and O in cooling) terminals on air
handler control.
De-energize indoor blower per ramping profile.
No
Yes
Cooling
Air Handler Control (AHC) Indoor Blower Mode Speed and Profile settings
1.
Set
Cooling Mode Blower Speed
jumper pin . (Low and high indoor blower CFM settings are identical for
cooling and heat pump)
2.
Set Blower Adjust Selection jumper pin.
3.
Set Cooling Mode Blower Ramping jumper pin (Cooling calls - All ramping profiles are active) (Heating calls -
Only ramping profiles 1 and 2 are active. If profiles 3 or 4 are selected, air handler control will default to profile 1.)
A
Profile 1 does not provide any ramping profiles.
B
Profile 2 provides a 30-second indoor blower ON delay at the start of a heat pump heating demand.
(45-second indoor blower
OFF
delay)
4.
Simultaneous Heat Pump and electric heat call: Indoor Blower will operate at the highest CFM requested by
the heat pump or the electric heat blower speed selection.
Single or Two-Stage Unit
1.
Air handler control on-board link must be cut between Y1 and Y2 to allow two-stage cooling operation.
Heating
NOTE — The outdoor unit control directly controls the outdoor
unit operation.)
NOTE — The outdoor unit control directly controls the
outdoor unit operation.
NOTE — The outdoor unit control
directly controls the outdoor unit
operation.)
NOTE — The outdoor unit control directly controls
the outdoor unit operation.
NOTE — The outdoor
unit control directly
controls the outdoor unit
operation.)
Yes
Yes
Yes
Yes
No
No
2.
Air handler control on-board link must be cut between R and O to allow heat pump operation.
CUT ON-BOARD LINK
Y1-Y2 FOR
TWO-STAGE A/C
Y1-Y2
2-STAGE
COMPR
R-O
HEAT
PUMP
R-DS
DEHUM
OR
HARMONY
CUT
FOR OPTIO
N
CUT ON-BOARD
LINK R -O.
NOTE
— USE FIGURE 19 AS A REFERENCE FOR SETTING JUMPER
CONFIGURATIONS ON THE AIR HANDLER CONTROL.
IMPORTANT
— USE CARE WHEN CUTTING LINKS TO
PREVENT DAMAGE TO CONTROL. SEE FIGURE 19,
BCE7S JUMP AND LINK GUIDE, FOR FURTHER
DETAILS.