506859-01
Issue 1236
Page 16 of 32
Table 5
5. Compare the subcooling value with those shown in Table
6. If subcooling is greater than shown, recover some
refrigerant. If subcooling is less than shown, add some
refrigerant.
Charge Using Approach Method (TXV System) - Outdoor
Temperatures 65°F or Above
The following procedure is intended as a general guide and
is for use on expansion valve systems only. For best results,
indoor temperature should be 70°F to 80°F. Monitor system
pressures while charging.
1. Record outdoor ambient temperature using a digital
thermometer.
2. Attach high pressure gauge set and operate unit for
several minutes to allow system pressures to stabilize.
3. Compare stabilized pressures with those provided in
Table 8. Minor variations in these pressures may be
expected due to differences in installations.
Significant
differences could mean that the system is not
properly charged or that a problem exists with some
component in the system. Pressures higher than
those listed indicate that the system is overcharged.
Pressures lower than those listed indicate that the
system is undercharged. Verify adjusted charge using
the approach method.
4. Use the same digital thermometer to check liquid line
temperature.
5. Subtract the outdoor ambient temperature from the liquid
line temperture to determine the approach temperature.
R-410A Temperature/Pressure Chart
Table 6
Subcooling Values
Temp.
°F
Pressure
Psig
Temp.
°F
Pressure
Psig
Temp.
°F
Pressure
Psig
32
100.8
74
214.0
116
396.0
33
102.9
75
217.4
117
401.3
34
105.0
76
220.9
118
406.7
35
107.1
77
224.4
119
412.2
36
109.2
78
228.0
120
417.7
37
111.4
79
231.6
121
423.2
38
113.6
80
235.3
122
428.8
39
115.8
81
239.0
123
434.5
40
118.0
82
242.7
124
440.2
41
120.3
83
246.5
125
445.9
42
122.6
84
250.3
126
451.8
43
125.0
85
254.1
127
457.6
44
127.3
86
258.0
128
463.5
45
129.7
87
262.0
129
469.5
46
132.2
88
266.0
130
475.6
47
134.6
89
270.0
131
481.6
48
137.1
90
274.1
132
487.8
49
139.6
91
278.2
133
494.0
50
142.2
92
282.3
134
500.2
51
144.8
93
286.5
135
506.5
52
147.4
94
290.3
136
512.9
53
150.1
95
295.1
137
519.9
54
152.8
96
299.4
138
525.8
55
155.5
97
303.8
139
532.4
56
158.2
98
308.2
140
539.0
57
161.0
99
312.7
141
545.6
58
163.9
100
317.2
142
552.3
59
166.7
101
321.8
143
559.1
60
169.6
102
326.4
144
565.9
61
172.6
103
331.0
145
572.8
62
175.5
104
335.7
146
579.8
63
178.5
105
340.5
147
586.8
64
181.6
106
345.3
148
593.8
65
184.3
107
350.1
149
601.0
66
187.7
108
355.0
150
608.1
67
190.9
109
360.0
151
615.4
68
194.1
110
365.0
152
622.7
69
197.3
111
370.0
153
630.1
70
200.6
112
375.1
154
637.5
71
203.9
113
380.2
155
645.0
72
207.2
114
385.4
73
210.6
115
390.7
72
207.2
114
385.4
73
210.6
115
390.7
Model
-24 -36 -48
-60
4SCU16 Temp. °F
5
6
6
9
4SCU18 Temp. °F
6
6
6
6
Содержание 4SCU 16LS Series
Страница 8: ...506859 01 Issue 1236 Page 8 of 32 Figure 9 Figure 10 ...
Страница 19: ...506859 01 Issue 1236 Page 19 of 32 Figure 14 CONTROL BOARD ...
Страница 24: ...506859 01 Issue 1236 Page 24 of 32 Information will be displayed but does not apply to this product ...
Страница 25: ...506859 01 Issue 1236 Page 25 of 32 ...
Страница 29: ...506859 01 Issue 1236 Page 29 of 32 4SCU16LS124 160 Wire Diagram ...
Страница 30: ...506859 01 Issue 1236 Page 30 of 32 4SCU18LS124 160 Wiring Diagram ...