background image

507607-03

Issue 1827

Page 21 of 23

Homeowner Information

In order to ensure peak performance, your system must 

be properly maintained. Clogged filters and blocked airflow 

prevent your unit from operating at its most efficient level.

Turn all electric power to unit OFF at disconnect 

switch(es) before performing any maintenance 

operations on system. Unit may have multiple power 

supplies. Electrical shock could cause personal injury 

or death.

 WARNING

Ask your dealer to show you where the indoor unit’s filter is 

located. It will be either at the indoor unit (installed internal 

or external to the cabinet) or behind a return air grille in the 

wall or ceiling in your home. Check the filter monthly and 

clean or replace it as needed.

Disposable  filters  should  be  replaced  with  a  filter  of  the 

same type and size. If you are unsure of the filter you need 

for your system, contact your dealer.

Many indoor units are equipped with reusable foam filters. 

These filters can be cleaned with a mild soap and water 

solution. Rinse the filter thoroughly and let dry completely 

before returning to unit or grille.

The filter and all access panels must be in place any 

time the unit is in operation.

Some systems are equipped with an electronic air cleaner, 

designed to remove the majority of airborne particles from 

the air passing through the cleaner. If your system includes 

an electronic air cleaner, ask your dealer for maintenance 

instructions.

Inspect and clean indoor coil. The indoor evaporator coil 

is equipped with a drain pan to collect condensate formed 

as the system removes humidity from the inside air. Have 

your dealer show you the location of the drain line and how 

to check for obstructions. This also applies to an auxiliary 

drain, if one is installed.

Inspect and clean outdoor coil:

Make sure no obstructions restrict airflow to the outdoor 

unit. Leaves, trash, or shrubs crowding the unit can cause 

it to work harder and use more energy. Keep shrubbery 

trimmed away from the unit and periodically check for 

debris which collects around the unit.

The outdoor coil may require frequent cleaning, depending 

on environmental conditions. Clean the outdoor coil with an 

unpressurized water hose to remove surface contaminants 

and debris. It may be necessary to flush the outdoor coil 

more frequently if it is exposed to substances which are 

corrosive or which block airflow across the coil (such as 

pet urine, cottonwood seeds, etc.).

Содержание 4SCU 16 LS Series

Страница 1: ...personal injury death or property damage Use appropriate safety gear including safety glasses and gloves when installing this equipment WARNING Risk of electrical shock Disconnect all remote power sup...

Страница 2: ...lbs Service Port Caps 8 ft lbs Sheet Metal Screws 16 in lbs 8 Machine Screws 16 in lbs 10 Machine Screws 28 in lbs Compressor Bolts 90 in lbs Inspection of Shipment Upon receipt of equipment carefull...

Страница 3: ...it properly can result in personal injury or death WARNING Line voltage is present at all components when unit is not in operation on units with single pole contactors Disconnect all remote electric p...

Страница 4: ...to terminal C Single wire to terminal C Unused wires Unused wires Comfort Sync Thermostat with a Non Communicating Outdoor Unit ENABLED FURNACE Comfort Sync THERMOSTAT NON COMMUNICATING OUTDOOR AIR CO...

Страница 5: ...evice section Refrigerant Piping If the 4SCU16 LS unit is being installed with a new indoor coil and line set the refrigerant connections should be made as outlined in this section If an existing line...

Страница 6: ...ne only 8 8 Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 intervals then strap the liquid line to the vapor line Floor Joist or Roof Rafter Metal Sleeve Floor Joist or Roof Rafter...

Страница 7: ...507607 03 Issue 1827 Page 7 of 23 Figure 9 Refrigerant Line Sets Installing Vertical Runs Figure 10 Flushing Connections...

Страница 8: ...voltage and line voltage connections to the new outdoor unit Do not turn on power to the unit or open the outdoor unit service valves at this time 4 Remove the existing R 22 refrigerant flow control o...

Страница 9: ...ling the higher system operating pressures The gauges should be rated for use with pressures 1 800 on the high side and a low side of 30 vacuum to 250 psi with dampened speed to 500 psi Gauge hoses mu...

Страница 10: ...w R410A into the line set and indoor unit Weigh in a trace amount of R410A A trace amount is a maximum of 2 oz of refrigerant or 3 lbs pressure Close the valve on the R410A cylinder and the valve on t...

Страница 11: ...et disconnect the manifold hose from the vacuum pump Open the service valves to break the vacuum in the line set and indoor unit Start Up If unit is equipped with a crankcase heater it should be energ...

Страница 12: ...perature 5 When the heating demand has been satisfied switch the thermostat to cooling mode with a set point of 68 F When pressures have stabilized use a digital thermometer to record the liquid and s...

Страница 13: ...5 50 45 40 55 50 45 40 55 50 45 40 ON OFF 30 PSC LO PS HI PS Y1 OUT Y2 OUT OUT O R I I C DS O Y1 Y2 L W COIL AMB DIS OPEN OFF OPEN 90 F 2ND STAGE LOCK IN 55 F 50 F 45 F 40 F DEFROST TERMINATION 100 F...

Страница 14: ...unit control circuit is isolated from power and the field supplied relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that the unit is ope...

Страница 15: ...ers Verify configuration of system Communicating systems only Reconfigure the system Replace control if heating or cooling is not available Only applicable in the communicating mode not in startup Exi...

Страница 16: ...he recommended upper limit of 279 F Discharge line high temperature error count reached 5 strikes Confirm that the system is properly charged with refrigerant Check system operating pressures and comp...

Страница 17: ...C 2AC 1 Stage AC 1HP 1 Stage AC 2HP Power Up 7 Segment Display String 2 H P ___ ___ ___ ___ ___ ___ Unit Type Stages No Capacity No Fan Profile Power Up Reset following display of self discovered conf...

Страница 18: ...1 E pause 250 pause E pause 231 Next codes up to 10 are shown using same method If there are no error codes stored E pause 000 Fault Memory Clear After the fault memory is cleared the following string...

Страница 19: ...ode string d pause F Outdoor fan RPM pause A ambient temp displayed pause repeat mode IMPORTANT On 2 stage unit R to DS link must be cut and correct RPM outdoor fan profile selected for outdoor fan to...

Страница 20: ...will automatically exit Field Test Mode If 10 second period expires or push button is held for less than 3 seconds control will automatically exit Field Test Mode and go into Idle Mode without storin...

Страница 21: ...nd all access panels must be in place any time the unit is in operation Some systems are equipped with an electronic air cleaner designed to remove the majority of airborne particles from the air pass...

Страница 22: ..._____________ Rated Load Ampacity _______________ Compressor Amperage _________________ OutdoorFan _____________________ Maximum Fuse or Circuit Breaker ____________________________ Electrical Connect...

Страница 23: ...507607 03 Issue 1827 Page 23 of 23 Figure 15 4SCU16LS124 36 48 60 Wiring Diagram...

Отзывы: