General Maintenance

General

• 

All Armcor equipment is designed for easy 

maintenance.

• 

Preventative maintenance programs will vary 

according to actual operating conditions and location 

and hours of usage by the client.

• 

Armcor Air Solutions are pleased to provide expert 

advice on special service maintenance requirements 

for particular installations.

IMPORTANT: Failure to carry out regular maintenance 

with a licensed and reputable service company may 

render warranty claims invalid if faults have been 

caused by lack of proper maintenance. 

Armcor Air Solutions may request to see the 

maintenance schedule carried out.

Monthly Maintenance Schedules

• 

Monthly maintenance is usually focused on air 

filters and visual checks to monitor any operational 

deficiencies. The type of filter and frequency of 

cleaning should be addressed by the installing 

contractor to suit the customer’s requirements.

• 

Filters should be inspected immediately after 

installation to confirm the frequency of cleaning 

needed for the particular location. Regular change/

clean of filters is necessary to ensure normal 

operating conditions.

• 

Check condensate drain (if applicable) for free 

drainage.

Guide to How Frequency 

According to Usage is Established

• 

Disposable Corrugated Filters. 

 

Ordinary disposable corrugated filters should last 

approximately one month in normal commercial use, 

or longer depending on usage.

• 

Cleanable Filters. 

 

If filters are cleanable, they should be cleaned once a 

month and the filter media should be replaced every 

12 months.

Three Monthly Checks 

Maintenance Schedules

• 

Repeat the monthly schedule.

• 

Check blower wheels for dirt build-up.

• 

Check all cabinet panels for correct fitting, alignment 

and seals, and clean cabinets as required. Ensure no 

insulation has been detached from the panels.

• 

All electrical terminals should be checked for 

tightness.

 

IMPORTANT

 – Ensure the main switch is turned off.

• 

Check and clean heat exchangers, heating/cooling 

coils, drain trays and outlets. (if applicable). Vacuum 

or brush clean as necessary.

Annual Maintenance Schedules

• 

Repeat monthly and three-monthly checks.

• 

Check cabinet for any paint chips or abrasions and 

treat accordingly.

• 

Check and record the available voltage and amperage 

of each phase.

• 

Check and record the amperage of each motor 

against nameplate details.

• 

Check and record refrigerant gas pressures (if 

applicable).

  HTC – Humidity and Temperature Control Unit Installation and Operation Manual 2021                    11

Содержание HTC500

Страница 1: ...Installation and Operation Manual HTC Humidity Temperature Control Unit HTC500 HTC6000 M ADE A U STRALI A N Manufactured byArmcor M ADE A U STRALI A N Manufactured byArmcor...

Страница 2: ...ments Mains Power Supply and Fusing Standard Equipment Layout 8 Features 9 General Maintenance 11 General Monthly Maintenance Schedules Guide to How Frequency According to Usage is Established Three M...

Страница 3: ...stems cope well with recirculated return air temperatures up to 24 C the HTC can be designed to cope with much higher air on conditions Humidity control involves reducing the temperature below dew poi...

Страница 4: ...eat recovery and or air handling equipment Installing and servicing equipment can be hazardous due to electrical and mechanical components When working on equipment observe precautions in all literatu...

Страница 5: ...he supply and return ducts to reduce any vibration transfer Fresh Air Inlet The location of the fresh air inlets must adhere to the Australian Standards AS 1668 2 The fresh air intake should be positi...

Страница 6: ...s and guidelines Wear safety goggles work gloves work boots and protective clothing All external units are provided with substantial lifting lugs on each corner at the base frame NOTE All units should...

Страница 7: ...issioning Where a Heat Exchanger is incorporated in the equipment warranty will be void if filters are not fitted IMPORTANT NEVER OPERATE A UNIT WITHOUT FILTERS FITTED TO THE FRESH AIR INTAKE Electric...

Страница 8: ...Standard Equipment Layout Supply Air Fresh Air Condensor Fan Condensor Reheat EC Plug Supply Fan DX Coil Filters 8 HTC Humidity and Temperature Control Unit Installation and Operation Manual 2021...

Страница 9: ...peration after the unit has stabilised Compressor Control Board TX Valve All TX valves have adjustment for super heat settings 8 11K is acceptable for R407C and R4100 gases HTC Humidity and Temperatur...

Страница 10: ...ransport and for the operation of the compressor Electrical Connection Tighten all electrical connections before starting and commissioning unit Phase Failure Relay Fan Control Card Adjust pots for sp...

Страница 11: ...ndensate drain if applicable for free drainage Guide to How Frequency According to Usage is Established Disposable Corrugated Filters Ordinary disposable corrugated filters should last approximately o...

Страница 12: ...riginal service call costs in identifying a warranty claim Freight and travel changes for work performed or parts supplied outside of all capital cities in Australia Field wiring refrigerant pipe run...

Страница 13: ...ng transport Leak test all caps and pressure connections after commissioning Starting Unit Check fans and Air Flow Turn on all circuit breakers Turn on control circuit and activate fans Turn on supply...

Страница 14: ...Amps Indoor Fan Motor Amps Boost Heater Element Amps Total Unit Amps Thermostat Settings C Thermostat Operating Correctly Y N Contactors Relays Operating Correctly Y N All Terminals Checked for Tightn...

Страница 15: ...Fresh Air Temperature C DB C WB 2 Air off Heat Exchanger C DB C WB 3 Air off Cooling Coil C DB C WB 4 Air off Heat Exchanger Supply Air C DB C WB Notes HTC Humidity and Temperature Control Unit Insta...

Страница 16: ...u P 03 8301 9200 109 111 Northcorp Blvd Broadmeadows Vic 3047 2021 Armcor Air Solutions reserves the right to alter products and specifications without notice and does not accept responsibility for po...

Отзывы: