background image

ARITERM SWEDEN AB

 

 

Installation, Operation & Maintenance - 

2009.02.18- 7/20

 MOUNTING OF DOCKNING PLATE AND SERVICE RAIL

Mount the secondary air tube, service rail and quick-release hand hold as shown in the photo-

graph.

Use the door frame as a template for drilling the four holes for the boiler’s 
stud bolts in the docking plate. In some cases, the docking plate’s outer di-

mension must be adapted to fit the boiler. It is easiest to use a circular saw.

 

Mount the plate against the boiler frame with heat-resistence glass fibre 

reinforced sealing strip or furnace cement, which can easily be applied 
afterwards through the mounting plate opening. Tighten while making sure 
the plate is not deformed. Final tightening of the service rail is to be done 
only once the burner has been attached and secured to the mounting plate. 
The service rail is to be pressed up against the boilers guide pins and outer 
clamping bolts are to be securely tightened. Check that the burner is cent-
red on the mounting plate’s guide pins when it is pulled out and pushed in. 
It is a good idea to lubricate the guide arms.

2

3

4

1

Mounting plate

1. 

Quick-release hand hold

2. 

Packing

3. 

Service rail

4. 

Secondary air tube

5. 

5

2

The fully assembled 
mounting plate and 
service rail.

The service rail should be loosely installed on the 

mounting plate and secured only after the burner 

is in place.

Electric cables should be installed such that they 

must be disconnected before the burne can be 
withdrawn from the boiler.

Содержание BeQuem 50

Страница 1: ...ARITERM SWEDEN AB Installation Operation Maintenance 2009 02 18 1 20 INSTALLATION OPERATION AND MAINTENANCE BeQuem 50 ...

Страница 2: ...NG Delivery The manufacturer has insured the burner in case of damages during transport from the factory to the first interim storage location Upon delivery it is important to check the condition of the burner before the burner is taken into use If any damage is found the seller shall be notified thereof without delay for possible claims Storage The burner can be stored outdoors protected from rai...

Страница 3: ...ntrol sensor 17 Chain 7 11 3 9 8 1 5 6 7 2 10 14 13 15 16 12 17 4 TECHNICAL DATA Performance Output using pellets Combustion efficiency Power of ignition resistor Normal power consumption 25 50 kW 95 450 W 90 W Dimensions Length outside the boiler Width outside the boiler Length inside the boiler Weight approx Smallest insertion opening width height Required combustion space above the combustion h...

Страница 4: ...it can be ignited manually when necessary The electric ignition system of the burner will only be acti vated in case the temperature of the boiler has dropped at least 8 C below the target temperature During heating the necessary ignition cycles take place by means of em bers in the combustion head saving electric energy The burner and the incorporated feeding system operate automatically The oper...

Страница 5: ...burner servicing Any condensation should be checked by visual inspection of the chimney s upper reach during various weather conditions In the event condensation runs through the flue a condensation vessel should be installed in the lower part of the chimney in order to tap off the condensation water Do not cover the combustion air intake ELECTRICAL INSTALLATION The supply cable delivered with bur...

Страница 6: ...ARITERM SWEDEN AB Installation Operation Maintenance 2009 02 18 6 20 WIRING DIAGRAM ...

Страница 7: ...ighten while making sure the plate is not deformed Final tightening of the service rail is to be done only once the burner has been attached and secured to the mounting plate The service rail is to be pressed up against the boilers guide pins and outer clamping bolts are to be securely tightened Check that the burner is cent red on the mounting plate s guide pins when it is pulled out and pushed i...

Страница 8: ...me the operation light turns green and the speed of the fan decreases Feeding of fuel stops completely within three minutes in order to give time for the fuel to ignite in the combustion head After this pellets are fed at low power for further five minutes After a full stop lasting ten minutes 7 starts the operation program switches on and controls the burner functions Only until at this point the...

Страница 9: ...ERATING TIME EL 2 POWER HIGH FAN 2 64 POWER LOW FAN 2 64 POWER MIN FAN 2 0 Power menu is available when nr 0 is changed to nr 5 Move forward when nr on display stops winking Fun must be in operation before function of the ignition element can be found Change nr 0 to nr 3 when El STEP using Electric heating is available when nr 3 is selected in EL STEP menu Only Biomatic function Press right arrow ...

Страница 10: ... Operating time high Operating time at high power Operating time low Operating time at medium power Operating time min Minimum power level during operating time only displayed when the min operating level is activated Operating time electric el1 Operating time of the resistor 1 The number of electric resistors vary bet ween models Biomatic function Operating time electric el2 Operating time of the...

Страница 11: ...by pressing the Plus button Description of menu 3 Power Power In order to activate this menu select number 5 in the Service Power menu by pres sing the Plus button Wait until the number stops flashing and continue by pressing the arrow but ton to the right Text on the display Description Setting possibilities Power 0 The menu is activated by entering code 5 Wait until the number stops flashing and...

Страница 12: ...UTPUTS Press plus key POWER 0 ENGLISH ADDRESS DEFAULT SEITINGS v0906 DIFF TANK NEJ AUGER EXTERNAL 0 FAN 0 FAN 2 0 AUGER BURNER 0 IGNITION 0 ALARM 0 EL STEP 0 Service meny shows when pushing same time buttoms and for 5 sec MAIN MENU SERVICE MENU POWER MENU Menu is only seen when OFF set chosen FUEL PELLETS FUEL PELLETS EL FUEL EL AUGER EXTERNAL TIME MAN 15min HOT STARTS BURNER X COLD STARTS BURNER ...

Страница 13: ...dy that the motor shaft rotates the auger and the motor of the external auger operates In most cases the default setting of the operating time of the external auger 30 seconds is not long enough to bring suf ficient amount of pellets to the burner If the problem cannot be removed by me ans of the above checks and remedies the operating time of the external auger may be too short In such cases incr...

Страница 14: ...not detected light du ring a certain period of time No fuel has entered into the combus tion head is there fuel in the upper connection If there is no fuel in the upper con nection of the burner check the cable connections of the level switches If this does not help wipe the level swit ches clean If the external feed of the burner does not start in spite of this or the level switches must be clean...

Страница 15: ...es stuck together in the combustion head in good time Such particles must absolutely be removed from the combustion head at short intervals to prevent over heating of and thus dama ge to the primary air ring Sintering is often caused by impurities in the fuel and the fuel supplier shall be notified immediately of such problems See also paragraph Advice about fuel pellets Note Handle ash always car...

Страница 16: ...ews within the cup must be carefully cleaned to ensure flawless operation Pull the flame control sensor gently out of the pipe Clean the flame control sensor Clean the flame controller metal pipe so that the ash in the pipe will not hinder the operation of the flame control sensor MAINTENANCE CARE SWEEPING Check the condition of the chain and wheels regularly Change worn out parts when necessary ...

Страница 17: ... must be taken into consideration FUEL RECOMMENDATION Raw material Chemically untreated barkless wood Diameter 8 mm Length 15 to 32 mm Volume weight over 600 kg m3 Moisture content less than 10 Ash content less than 0 7 weight Fine material content max 4 weight Melting temperature of ash 1100 C Energy content 4 75 kWh kg ADVICE ABOUT FUEL PELLETS Actions in emergency situations Fire If the heating...

Страница 18: ...ARITERM SWEDEN AB Installation Operation Maintenance 2009 02 18 18 20 DECLARATION OF CONFORMITY NOTES ...

Страница 19: ...water reaches desired temperature boiling risk If these instructions are not followed during installation operation and maintenance the obligations of Ariterm AB under the warranty regulations are no longer binding Ariterm reserves the right to alter any details and specifications without prior notice Flue gas temp High CO O2 CO2 Air fuel ratio Efficiency Draught i mm Fan Effect Flue gas temp Low ...

Страница 20: ...ARITERM SWEDEN AB Installation Operation Maintenance 2009 02 18 20 20 Ariterm Sweden AB Flottilvägen 15 39241 Kalmar Sweden www ariterm se 46 480 442850 ...

Отзывы: