EV1000 Series PIRs
3
Installation Instructions
EN
Installation instructions
Introduction
The EV1000/1000AM family is made up of PIR/PIR-AM motion
sensors. They have a patented mirror, pyro and signal processing
technology.
Installation guidelines
The technology used in these detectors resists false alarm
hazards. However, avoid potential causes of instability such as
(see Fig.
!
):
Direct sunlight on the detector.
Heat sources within the detector field of view.
Strong draughts onto the detector.
Large animals within the detector field of view.
Objects within 50 cm (20 in.) of the anti-masking (AM)
detector.
Obscuring the detector field of view with large objects, such
as furniture.
Installing two detectors facing each other and less than
50 cm (20 in.) apart.
Installing the detector
1.
Lift off the custom insert and remove the screw if enclosed
(see Fig.
"
, step 1).
2.
Using a screwdriver, carefully prise open the detector (see
Fig.
"
, steps 2 and 3).
3.
Fix the base to the wall between 1.8 m and 3.0 m (5.9 and
9.8 ft.) from the floor. For flat mounting use a minimum of two
screws (DIN 7998) in positions A. For corner-mounting use
screws in positions B or C (Fig.
#
). To install a pry-off tamper,
use position A or C.
4.
Wire the detector (see Figs.
#
and
'
).
5.
Select the desired jumper and DIP switch settings (see
Fig.
%
). See section
Setting the detector
for more information.
6.
Remove the blinders and add the stickers, if required (see
Fig.
&
for an example)
7.
For ceiling-mount applications that require a 90° coverage
use the SB01 swivel-mount bracket.
8.
Close the cover.
9.
Insert the screw (if required) and place the custom insert.
Setting the detector
Jumper settings
See figure
%
for the jumper locations in the detector.
J1: Not used
J2: PIR enabling the LED
On:
Enables the detector LED at all times (ex-factory).
Off:
Puts the LED under control of the control panel and
disables the detector LED at all times (no memory
feature).
J3 and J4: Dual loop setting
This sets the alarm and tamper relays. It allows you to connect the
detector to any control panel. Use jumpers 3 and 4. See figure
'
.
J5: D/N mode (Day/Night) or Rtest (remote test) setting
Use this jumper to set terminal 8 to either D/N or Rtest.
GE Security recommends that you use D/N to manage the AM/TF
activation when required. Use Rtest to test the detector from the
control panel. The detector will activate the Alarm relay if the test
result is positive, and the AM relay if the test result is negative.
Terminal 8 = D/N
Ex-factory
Terminal 8 = Remote test
J6: Polarity setting of the control voltage (CV)
On:
“Active High” provides the standard GE Security logic with
“Active High” logic to enable
Walk Test (WT)
and
Day/Night
inputs.
Off: “Active Low” provides “Active Low” logic to enable
Walk Test
and
Day/Night
inputs.
Active High
Ex-factory
Active Low
DIP switch setting
SW 1: When to signal AM (anti-masking) or TF (technical fault)
output
On:
Signals AM or TF only when the system is in Day mode (ex-
factory).
Off:
Always signals AM or TF during Day and Night mode.
SW 2: AM sensitivity
On: Selects a higher level of AM sensitivity. AM relay reacts within
6 seconds.
Off:
Selects the standard AM sensitivity. AM relay reacts within
12 seconds (ex-factory).
SW 3: Resetting the AM/TF output
The system will only reset an AM alarm if it has ensured that the
cause of the AM alarm has been removed. If the AM circuitry
cannot return to its original reference levels, then either the
detector is still masked or possibly has been damaged. The owner
should then visually check that the detector is still fully functional.
On
:
Resets the AM or TF status 40 seconds after a PIR alarm.
Off
:
Resets the AM or TF status after a PIR alarm when the
system is in Day and Walk Test status. The yellow LED will
blink quickly. When the system is in Night status, the yellow
LED will turn off and the system is reset (ex-factory).
SW 4: Signaling AM or TF output
This DIP switch is not used with the AMZ version of
detectors.
On
:
Signals AM on both the AM and Alarm relays. Signals TF on
the AM relay only.
Off
:
Signals AM and TF on the AM relay (ex-factory)
SW 5: Setting LEDs
On:
Enables both LEDs on the detector at all times (ex-factory).
Off: Puts both LEDs under the control of the Walk Test and
Day/Night input. This activates the memory feature of the
detector.
LED indication
Continuously on
Normal blinking (1 Hz)
Fast blinking (4 Hz)
PIR
Red
LED
Yellow
LED
Alarm
relay
AM relay
To reset
Start up
Closed
Automatically
after
25 s
Low voltage
Open
(Alarm)
Apply correct voltage
PIR intruder
alarm
Open
(Alarm)
Automatically
after
3 s
PIR/AM Red
LED
Yellow
LED
Alarm
relay
AM relay
To reset
Start up
Closed Closed
Automatically after
60 s
Low voltage
Open
(Alarm)
Open
(Alarm)
Apply correct voltage
PIR intruder
alarm
Open
(Alarm)
Automatically
after
3 s
Latched PIR
(Memory)
Switch toNight mode
AM alarm
Open*
(Alarm)
Open
(Alarm)
See DIP switch 3
After AM
reset
Switch to Night mode
Technical
fault
Open
(Alarm)
Do a successful walk
test
* Depends on the setting of the DIP switch SW4.
Technical specifications
EV1012
EV1012AMZ
EV1012AM
Detector
PIR
PIR + AM
Signal processing
DSP
Range 12
m
Optical
9 high-density mirror curtains
Memory No
Yes
Input power
9 VDC to15 VDC (12 V nominal)
Peak-to-peak ripple
2 V (at 12 VDC)
Detector start-up time
25 s
60 s
Normal current
consumption (mA)
4.4 3.8
10
Current consumption in
Alarm (mA)
1.2 3.9
3.8
Max. current consumption
(mA)
11 24
24
Mounting height
Min. 1.8 m, max. 3.0 m
(Min. 5.90 ft., max. 9.84 ft.)
Target speed range
30 cm/s to 3 m/s
(1 ft./s to 10 ft./s)
20 cm/s to 3 m/s
(4 in./s to 10 ft./s)
Alarm (NC) / Tamper relay
characteristic
80 mA
30 VDC
non 80
mA
30 VDC
Pry-off tamper
Optional
On-board (Yes)
AM relay characteristic
—
80 mA at 30 VDC max.
Alarm time
3 s
Operating temperature
-10°C to +55°C (14°F to 130°F)
Dimensions
(H x W x D)
108 × 60 × 46mm (4.25 × 2.36 × 1.81 in.)
Relative humidity
Max. 95%
Weight
120 g (4.2 oz.)
128 g (4.5 oz.)
IP/IK rating
IP30 IK02