8
3. Available Aux/Battery current based on backup
Time (h)
Current (mA)
Battery capacity
Approval
Grade
Discharge
Charge
Output
7.2Ah
18Ah
25Ah
36Ah
50Ah
Aux 490 1300 1800 1800 1800
EN 1&2
12 72
Battery 2235 1425 925 925 925
Aux 40 220 330 500 550
EN 3&4
60 24
Battery 2685 2500 2395 2225 2175
Aux 110 360 550 850 1000
Nfa2p
ΙΙ
36 30
Battery 2615 2350 2200 1875 1725
Aux 20 150 230 380 580
Nfa2p
ΙΙΙ
72 30
Battery 2700 2600 2500 2345 2100
Aux 150 500 700 1050
1100
VdS
B
30 24
Battery 2575 2225 2025 1675 1625
Aux 40 220 330 500 550
VdS
C
60 24
Battery 2685 2500 2395 2225 2175
4. General Feature Specifications
End of line resistor (standard)
4.7 k
Ω
5% 0.25 W (2.2 k
Ω
or 10 k
Ω
)
Standard on board output
Ext.siren (J13 - S+/S-)
Electronic output
Rating: 1 A at 13.8 VDC
Housing Dimensions
ATS1203: 370 x 475 x 160mm
ATS1204: 460 x 475 x 160mm
Colour Beige
Operating temperature
0° to + 50 °C (cer5° +40°C)
Humidity
95% non condensing
Environmental
IP protection grade
IP30
5. Fuses
F4
Auxiliary power & siren
F2 A, 20x5
F5
Battery
F3 A, 20x5
Mains fuse *
F630 mA, 20x5
* Mains Fuse is part of the mains terminal block.
WARNING!
Before removing the mains fuse, mains power must be disconnected (see page 4)!
!