Technical specification:
Supply voltage ................................... 17 to 28 VDC
Current consumption @ 24 VDC:
Switch on surge ............................. < 1.2 mA
Standby ......................................... 310 µA
Alarm (Sounder) ............................ 5.1 mA
Alarm (Beacon) .............................. 3 mA
Peak Sound Level @ 90º ± 3 dB(A) .... 97dBA dBA at 1m*
Number of Tones ............................... 32
Frequency Range .............................. 400 - 2850 Hz*
Volume Adjustment ………………….. 8db (Typical)
Synchronisation ................................. Automatic
Casing ............................................... High Impact
Polycarbonate
IP rating (shallow base) ..................... IP21
IP rating (deep base) ......................... IP65
Cable size .......................................... min. 0.28 mm
2
/
max. 2.5 mm
2
Operating temperature ....................... -10°C to +55°C
Storage temperature ......................... -10ºC to +55ºC
Relative humidity (non condensing)...... 5% to 95%
Dimensions (shallow base) (dia x h) .... 100 x 81 mm
Dimensions (deep base) (dia x h) ..... 100 x 104 mm
Weight (shallow base) ....................... 215 g
Weight (deep base) ........................... 250 g
Device Type Code ............................. 0E (H)
*depends on selected tone and input voltage. See tone table for
details. Certified on tones 1,2,3,6,7 & 13 only.
AS2300 Series Loop Powered Sounders & Sounder/Beacons
Electrical connections
Electrical connections marked on the product are as follows:
L+ = Line (positive)
L- = Line (negative)
E = earth / screen
Note:
The separate earth terminal is provided on the deep base
for connecting the screen or functional earth. On the shallow
base, terminal 5 can be used for this
purpose. (See figures 1 and 2)
Addressing
Each device requires a numeric address between 1 and 128 for
identification purposes. This is set using switches 1-8 on the
Address Selector DIP switch (see Figure 3a). See the table at the
end of this document for a complete list of address settings.
When the AS2366 or AS2367 is used in conjunction with the
FP1200/2000 range of fire panels, the device must have an
address of 80 or higher when it is used as a sounder and beacon.
When an address lower than 80 is assigned to the device, it will
function as a sounder only, without the beacon flashing.
Tone selection and volume control
The device tone is set using switches 1-5 on the Tone Selector DIP
switch (see Figure 3b). See the table at the end of this
document for a complete list of tone / DIP switch settings.
Switch 6 on the Tone Selector DIP switch is used to select the
sound volume (See figure 3c). The default setting (switch OFF)
is high volume. Changing the switch to ON reduces the sound
output by 8dB.
Locking mechanism
To lock a sounder onto the base, remove the locking tab on the
base as shown in Figure 4, before attaching the sounder.
To remove a locked sounder,
●
Remove the small rubber bung from the hole on the
side of the sounder.
●
Insert a screwdriver (or similar) into the hole and press
the clip at the same time as twisting the sounder head.
Note:
the O-ring and bung must be fitted to maintain the
weatherproofing.
Maintenance and testing
Basic maintenance is reduced to an annual inspection.
Do not modify internal wiring or circuitry. Test all devices after
installation.
Troubleshooting
Before investigating individual units for faults, check the system
wiring is fault free. Earth faults on data loops may cause
communication errors.
Common problems and causes are:
Problem
Possible Cause
No response or
Incorrect address setting or incorrect
missing
loop wiring (polarity reversed)
Device fails to
Control panel has incorrect cause and
operate
effect programming
Products marked with this symbol cannot be disposed of as
unsorted municipal waste in the European Union. For proper
recycling, return this product to your local supplier upon the
purchase of equivalent new equipment, or dispose of it at
designated collection points.
For more information see: www.recyclethis.info.
Certification and approvals information
Product code
AS2363, AS2364, AS2363W, AS2364W
AS2366, AS2367, AS2366W, AS2367W,
AS2366WY, AS2367WY
Description
Addressable Sounder and Sounder/Beacon
Certification
Compliance
EN54-3 Type A
CPD certification BRE Global Ltd and LPCB
body
CPD certificate
AS2363, AS2363W: 0832-CPD-1342
number
AS2364, AS2364W: 0832-CPD-1343
AS2366, AS2366W, AS2366WY: 0832-CPD-1344
AS2367, AS2367W, AS2367WY: 0832-CPD-1345
CPD certificate
The year of certification is included in the
year
first two digits of your product serial number
(located on the product identification label).
Technical Data
18-187051
Document