cated with the cylinder. The tundish must also be in a position visible to the occupants, and positioned away from 

any electrical devices. The discharge pipe from the tundish should terminate in a safe place where there is no risk to 

persons in the vicinity of the discharge and to be of metal.

2)  Discharge pipes from the temperature & pressure relief and pressure relief valve may be joined together.

 

3)  The pipe diameter must be at least one pipe size larger than the nominal outlet size of the safety device unless its 

total equivalent hydraulic resistance exceeds that of a straight pipe 9 m long.

  i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at least 2 sizes larger than the 

nominal outlet size of the safety device. Between 18 m and 27 m at least 3 times larger, and so on.

  Bends must be taken into account in calculating the flow resistance. See fig.1 and Table 2.

4)  The discharge pipe must have a vertical section of pipe at least 300 mm in length, below the tundish before any 

elbows or bends in the pipe work.

5)  The discharge pipe must be installed with a continuous fall.

6)  The discharge must be visible at both the tundish and the final point of discharge, but where this is not possible or 

practically difficult; there should be clear visibility at one or other of these locations. Examples of acceptance are:

i)  Ideally below a fixed grating and above the water seal in a trapped gully.

ii)  Downward discharges at a low level; i.e. up to 100 mm above external surfaces such as car parks, hard standings, 

grassed areas etc. These are acceptable providing that where children may play or otherwise come into contact with 

discharges, a wire cage or similar guard is positioned to prevent contact, whilst maintaining visibility.

iii)  Discharges at high level; i.e. into a metal hopper and metal down pipe with the end of the discharge pipe clearly vis-

ible (tundish visible or not). Or onto a roof capable of withstanding high temperature discharges of water 3 m from 

any plastic guttering systems that would collect such a discharge (tundish visible).

3) The pipe diameter must be at least one pipe size larger than the nominal outlet size

of the safety device unless it’s total equivalent hydraulic resistance exceeds that of a

straight pipe 9 m long.

i.e. Discharge pipes between 9 m and 18 m equivalent resistance length should be at

least 2 sizes larger than the nominal outlet size of the safety

device. Between 18

m and 27 m at least 3 times larger, and so on.

Bends must be taken into account in calculating the flow resistance.

See fig..5 and Table 2.

4) The discharge pipe must have a vertical section of pipe at least 300 mm in length,

below the tundish before any elbows or bends in the pipe work.

5) The discharge pipe must be installed with a continuous fall.

6) The discharge must be visible at both the tundish and the final point of discharge,

but where this is not possible or practically difficult; there should be clear visibility at

one or other of these locations. Examples of acceptance are:

i) Ideally below a fixed grating and above the water seal in a trapped gully.

ii) Downward discharges at a low level; i.e. up to 100 mm above external surfaces

such as car parks, hard standings, grassed areas etc. These are acceptable providing

that where children may play or otherwise come into contact with discharges, a wire

cage or similar guard is positioned to prevent contact, whilst maintaining visibility.

iii) Discharges at high level; i.e. into a metal hopper and metal down pipe with the

end of the discharge pipe clearly visible (tundish visible or not). Or onto a roof capable

15

600 mm Max.

300 mm

Min.

Temperature & pressure

relief valve

Metal discharge pipe (D1) from

temperature & pressure relief valve.

to tundish.

Metal discharge pipe (D2) from tundish

with continuous fall. See Table 2 and worked

example.

Tundish

Fixed grating

Trapped gulley

Discharge below

fixed grating.

(see page 6 for

alternative points

of discharge).

Fig.. 4

Suggest ways of terminating discharge pipes safely

42.0.01.07204.03 pag. 9-20.qxd:42.0.01.07204.01 pag. 9-20  7-10-2016  11:28  Pagina 15

 

iv)  Where a single pipe serves a number of discharges, such as in blocks of flats, the number served should be limited to 

no more than 6 systems so that any installation can be traced reasonably easily. The single common discharge pipe 

should be at least one pipe size large than the largest individual discharge pipe to be connected. If unvented hot 

water storage systems are installed where discharges from safety devices may not be apparent i.e. in dwellings oc-

cupied by the blind, infirm or disabled people, consideration should be given to the installation of an electronically 

Содержание PRO1 ECO 100V

Страница 1: ...UNVENTED WATER HEATER ...

Страница 2: ...tal capacity or lacking the requisite experience and familiarity unless under supervision or fol lowing instruction in the safe use of the appliance and the hazards attendant on such use DO NOT permit children to play with the ap pliance User cleaning and maintenance may not be done by unsu pervised children 6 DO NOT touch the appliance when barefoot or if any part of your body is wet 7 Before usi...

Страница 3: ... from the power grid when it is out of service in an area subject to subzero tempera tures 13 Water heated to over 50 C can cause immediate serious burns if delivered directly to the taps Children disabled persons and the aged are particularly at risk We recommend installing a thermostat ic mixer valve on the water delivery line marked with a red collar 14 Do not leave flammable materials in conta...

Страница 4: ...ter installations but existing national regulations remain in force This electronic storage water heater is sold with a thermal disinfection cycle function enabled by default Every time the product is switched on and every 30 days the thermal disinfection cycle runs to heat the water heater up to 60 C Warning when this software has been carrying out the thermal disinfection treatment water tempera...

Страница 5: ...roduct Data Sheet Enclosure A to this manual are defined in relation to EU Directives 812 2013 and 814 2013 The products without the label and the data sheet for water heaters and solar devices stipulated in regulation 812 2013 are not intended to be used in such assemblies The device is equipped with a smart function that allows you to adapt the consumption to the user profiles If operated correc...

Страница 6: ...ing Regulations The installer should check with the local water authority for confirmation of the maximum water supply pres sure Theapplianceshouldbeleftpackeduntilitisreadytobeinstalled Whenunpackingtakecarenottodamagethe temperature and pressure relief valve on the top of the heater A drain has to be provided for any water discharged through the safety valves A cold water supply pressure between...

Страница 7: ...upport a weight that is three times higher than the weight of the water heater filled with water Fastening hooks with a diameter of at least 12 mm are recommended To facilitate maintenance make sure there is a clearance of at least 50 cm inside the enclosure for access to the electrical equipment PLUMBING WARNING Note If a valve i e a non return valve water meter pressure reducing valve or any typ...

Страница 8: ...om relief valves must be made in a safe and conspicuous manner Please note that in all cases the dielectric junctions must be connected to the heater before any other connec tion is made these prevent an electrolytic reaction If the supplied Dieletric Junctions are not fitted this could void the warranty Only the use of copper pipe is recommended for connection to the heater If any other material ...

Страница 9: ... Discharge pipes between 9 m and 18 m equivalent resistance length should be at least 2 sizes larger than the nominal outlet size of the safety device Between 18 m and 27 m at least 3 times larger and so on Bends must be taken into account in calculating the flow resistance See fig 5 and Table 2 4 The discharge pipe must have a vertical section of pipe at least 300 mm in length below the tundish b...

Страница 10: ...lbows at 0 8 m each 3 2 m Therefore the maximum permitted length equates to 5 8 m As 5 8 m is less than the actual length of 7 m therefore calculate the next largest size Maximum resistance allowed for a straight length of 28 mm pipe D2 from G 1 2 T P valve equates to 18 m Subtract the resistance for 4 no 28 mm elbow at 1 0 m each 4 m Therefore the maximum permitted length equates to 14 m As the a...

Страница 11: ...rate control of the electrical system by verifying compliance with current safety standards which is adequate for the maximum power absorbed by the water heater refer to the data plate and that the section of the cables for the electrical connection is suitable and complies with local regulations The manufacturer is not liable for damage caused by lack of grounding or anomalous power supply Before...

Страница 12: ...he wire Ref Y and loosen the screws During reassembly make sure that all components are put back in their original positions In order to work on the heating element and the anode the appliance must first be emptied Undo the 5 bolts C fig 5 and remove the flange F fig 5 The heating element and anode are attached to the flange During reassembly make sure that the flange gasket the thermostat and the...

Страница 13: ...ration described above to confirm the reactivation of the led Ref 4 will flash rapidly for 4 sec Adjusting the temperature and activating the functions Fig 3 Press the button Ref A to switch on the appliance Set the desired temperature by using the and buttons to select a level between 40 C and 65 C During the heating phase the LEDs Ref 1 5 corresponding to the temperature reached by the water so ...

Страница 14: ...ut any obligation to purchase new product 18 LEDs with the other LEDs off Each press of the button increases or decreases the set temperature by 10 degrees After 5 seconds without any action the set point will be confirmed and memorised STALL STATUS There are two possible stall statuses TOUCH CONTROL STALL STATUS If a touch control error is detected the status of the touch LED is undetermined and ...

Страница 15: ...80 70 60 50 40 1 2 3 B A C 4 5 ECO 3 4 W Y T M G C 3 4 1 2 3 A B C 4 5 ...

Страница 16: ...me Schéma d installation Esquema de instalac stalacji Instalační schéma Installationsschema Montavimo schema Instalācijas shēma Schemat instalacji Instalacijski dijagram Schema de instalare Монтажна схема Dijagram instalacije Instalacijska shema Орнату схемасы Installatieschema Σύστημα ε H ...

Страница 17: ...Installation scheme Model A B C 50V 365 531 605 80V 570 736 810 100V 722 888 962 A Ø 470 440 B C 100 MODEL A B C 50V 365 531 605 80V 570 736 810 100V 722 888 962 ...

Страница 18: ...Ariston Thermo S p A Viale Aristide Merloni 45 60044 Fabriano AN Tel 39 0732 6011 ariston com 420011033100 05 2019 ...

Отзывы: