The boiler can be converted to use either methane (natural) gas (G20)
or LPG (G30 - G31) by an Authorised Service Centre.
The operations that must be performed are the following:
1. Replace the jets on the main burner (see table in section 4);
2. Adjust the maximum and minimum thermal capacity values for the boiler
(see table in section 4);
3. Replace the gas rating plate;
4. Adjust the maximum thermal power setting;
5. Adjust the soft-light feature;
6. Adjust the ignition delay feature for the heating system (can be set from 0
to 2 mins.).
CATEGORY II2H3+
Recommended Soft-
light Pressure
(mbar)
Methane
Gas
G20
8.0
Liquid
Propane
Gas
G31
16.0
Liquid
Butane
Gas
G30
16.0
4.1
C
HANGING THE
T
YPE OF
G
AS
The outlet pressure of the gas cock is obtained by completely loosening the
screw on the solenoid. The maximum pressure of the gas to the burner will
be equal to the nominal delivery pressure minus the head loss within the
gas valve.
[1 mbar = 10,197 mmc.a.]
4.
GAS ADJUSTMENTS
Lower Wobbe Index (15°C;1013mbar)
MJ/m3h
Nominal Delivery Pressure
mbar
Minimum Delivery Pressure
mbar
23 MFFI
Main Burner: n. 13 jets (ø)
mm
Consumption (15°C; 1013mbar)
mc/h
Consumption (15°C; 1013mbar)
Kg/h
Gas Cock Outlet Pressure
max - min
mbar
27 MFFI
Main Burner: n. 15 jets (ø)
Consumption (15°C; 1013mbar)
mc/h
Consumption (15°C; 1013mbar)
Kg/h
Gas Cock Outlet Pressure:
max - min
mbar
CATEGORY II2H3+
Methane Gas
G20
Liquid Butane Gas
G30
Liquid Propane Gas
G31
45.67
20
17
1.30
2.72
----
11.0 - 2.0
1.30
3.15
----
11.0 - 1.6
80.58
29
20
0.77
----
2.02
(*) - 6.0
0.77
----
2.34
(*) - 4.6
80.58
37
25
0.77
----
2.02
(*) - 6.0
0.77
----
2.31
(*) - 6.0