In Fig. 2.11 below, several different types of flue systems are shown.
For additional information regarding the flue accessories, please consult the
Flue Pipe Accessories manual.
Fig. 2.11
4 m
4 m
4 m
46 m
46 m
46 m
17 m
3 m
3 m
3 m
50 m
50 m
50 m
15 m
Maximum Extension
Exhaust/Air
27 kW 30kW
Exhaust
Type
Diameter
of Pipes
(mm)
Use of Restrictor on Discharge Side
42 mm 45 mm
27 kW 30 kW
Risk of
Condensation Forming
27 kW 30 kW
C12 (xx)
C32 (xx)
C42 (xx)
C12 (xy)
C32 (xy)
C42 (xy)
C52 (xy)
Coaxial
Systems
Twin Pipe
Systems
ø 60/100
ø 60/100
ø 60/100
ø 80
ø 80
ø 80
ø 80
L * < 0.5 m
L * < 0.5 m
L * < 0.5 m
L < 5 m
L < 5 m
L < 5 m
L < 5 m
L * < 0.5 m
L * < 0.5 m
L * < 0.5 m
L < 7.5 m
L < 7.5 m
L < 7.5 m
L < 7.5 m
L > 6.5 m
L > 6.5 m
L > 6.5 m
L < 5.3 m
L > 4.5 m
L > 4.5 m
L > 4.5 m
L > 4.5 m
(*) L = Length of Piping
In calculating the lengths of the pipes, the maximum length must also take into
consideration the values for the exhaust/air intake end terminals, as well as 90°
elbows for coaxial systems.
The C52 types must comply with the following requirements:
1. The discharge/intake vent pipes must have the same diameter of
ø
80 mm.
2. If an elbow is inserted into the discharge/ventilation system, the calculation of
the overall extension must take into consideration the values for each curve, as
indicated in the table.
3. The exhaust pipe must extend at least 0.5 m above the ridge of the roof if it is
located on a side other than that for the air intake (this is not obligatory if the
exhaust and air intake pipes are located on the same side of the building).
023A