background image

20

B023

The boiler is designed to make it easy to analyse the combustion by-products.

Using the especially designed apertures, readings can be taken on the
temperature of the combustion by-products and of the combustion air, as well
as of the concentrations of O

2

and CO

2

, etc.

The best maximum-power test conditions for the heating system are when the
selector “C” is turned to the flue analysis setting.

The discharge/ventilation of the exhaust fumes can be monitored to check for
losses in general pressure in the system. This is done to eliminate the cause of
lighting failure with the main burner not indicated by a shutdown status.
With a differential manometer connected to the test socket on the combustion
chamber, the DP value for the air pressure switch can be taken. The measured
value should not be less than 10 mbar under maximum thermal power
conditions (with the knob “C” on the flue test setting) in order for the unit to
function properly and without interruption.

- the potentiometer for the maximum thermal power for the heating system,

maximum thermal power setting (factory set at the maximum value, unless
indicated otherwise on the adhesive sticker located in proximity to the
potentiometer);

- The connection for the diagnostic device (TCS-TCS2).

G20

5.5 mm c.a.

G25

4.5 mm c.a.

G30-31

1.8 mm c.a.

The boiler is equipped with the following safety systems (see section 3.3 for
references):
1 - Ignition Failure
This control signals an ignition failure on the burner 7 seconds after a lighting
failure. The L.E.D. “B”.will turn on to signal the shutdown status.
The system can be reset by pressing and releasing the button “A” after
checking to make sure that the gas valve is open. Repeat this process until the
burner lights.
2 - Circulation Failure
This control signals that the safety pressure switch on the primary circuit has
not sensed a pressure of at least 1 bar within 40 seconds of the activation of
the circulation pump, it shuts off the boiler and lights the L.E.D. “D”. The system
can be reset (after the pressure has been brought up to the proper level) by
using the On/Off switch “L”.
3 - Overheating
This control shuts off the boiler in the case where the primary circuit reaches a
temperature in excess of 110°C. The L.E.D. “G” will come on to signal this shut

3.6

Combustion Analysis

3.7

Fume Discharge 
Monitoring

3.8

Boiler Safety Systems

Содержание EURO COMBI 47-116-10

Страница 1: ...A 23 MFFI A 27 MFFI G C N 47 116 10 47 116 12 Installation Instructions Type C Boilers LEAVE THESE INSTRUCTIONS ADJACENT TO THE GAS METER Country of destination GB...

Страница 2: ...10 Room Thermostat Connection 2 11 Electrical System Diagrams 2 12 Water Circuit Diagrams 3 COMMISSIONING 3 1 Initial Preparation 3 2 Removing the Front Panel 3 3 Control Panel 3 4 Initial Start up 3...

Страница 3: ...rse of the control panel The gas with which this appliance operates is also shown on the label at the bottom of the boiler Do not install this appliance in a damp environment or close to equipment whi...

Страница 4: ...er Consumption W 150 Protection Grade of Electrical System IP 44 Internal Fuse Rating FAST 2 AT Weight Kg 47 G C Number 47 116 10 4 B023 1 2 Technical Information chamber visually 4 Visual check of th...

Страница 5: ...8 Spark Generator 9 Diverter Valve 10 Main Circuit Temperature Probe 11 Main Circuit Flow Switch 12 Diverter Valve Microswitch 13 Filter Seat 14 Drain Valve 15 Secondary Heat Exchanger 16 Safety Valv...

Страница 6: ...om sealed appliance is installed in a room containing a bath or shower the boiler and any electrical switch or appliance control utilising mains electricity should be situated so that it cannot be tou...

Страница 7: ...ing Return 3 4 2 3 Overall Dimensions 890 3 6 5 A B D E C 465 In order to allow for access to the interior of the boiler for maintenance purposes the boiler must be installed in compliance with the mi...

Страница 8: ...as follows The yellow green wire should be connected to the terminal marked with the earth symbol make sure to re use the ferrule mounted on the other supply cord The blue wire should be connected to...

Страница 9: ...t loss and avoid freezing Particular attention should be paid to pipes passing through ventilated spaces in roofs and under floors By pass The appliance includes an automatic by pass valve which prote...

Страница 10: ...water carrying pipe work and must be used for pipe work carrying drinking water 2 9 Flue Connections Flue System The provision for satisfactory flue termination must be made as described in BS 5440 1...

Страница 11: ...rminal 1200 J From an opening in the car port e g door window into dwelling 1200 K Vertically from a terminal in the same wall 1500 L Horizontally from a terminal in the same wall 300 11 B023 A BC D E...

Страница 12: ...perforated ring 2 Use a tool to grasp the lid and remove it completely 3 Clean any burrs or sharp edges with a knife or an appropriate tool In Fig 2 10 below several different types of flue systems ar...

Страница 13: ...ues for each curve as indicated in the table 4 The exhaust pipe must extend at least 0 5 m above the ridge of the roof if it is located on a side other than that for the air intake this is not obligat...

Страница 14: ...itching wires from the time clock following points 1 7 above 10If using a time clock and room thermostat these must be connected in series as per points 1 9 above Note Only a two wire type room thermo...

Страница 15: ...stment P Time Clock Connection Q On Off L E D R On Off Switch S Interface Wire for P C B s T Relay Motorised Valve U Ignitor Relay V Gas Valve Relay W Fan Relay X Circulation Pump Relay Aa Adaptor Bri...

Страница 16: ...16 B023 A 23 MFFI A 27 MFFI EX C MI FFI 8 A 23 MFFI A 27 MFFI...

Страница 17: ...full turn and leave open permanently Close all air release valves on the central heating system Gradually open valve s at the filling point filling loop connection to the central heating system until...

Страница 18: ...ocated on the top edge of the panel 2 Lift and unhook the panel system sect 3 4 and run it until the temperature has reached the boiler operating temperature The system must then be immediately flushe...

Страница 19: ...ves are open 4 Turn on the gas cock and check the seals on the connections including the one for the burner making sure that the meter does not signal the passage of gas Check the connections with a s...

Страница 20: ...setting factory set at the maximum value unless indicated otherwise on the adhesive sticker located in proximity to the potentiometer The connection for the diagnostic device TCS TCS2 G20 5 5 mm c a G...

Страница 21: ...low 0 C during the winter This makes repeated draining of the entire system unnecessary Draining the domestic hot water system Whenever there is the danger of the temperature dropping below the freezi...

Страница 22: ...als replacement of any faulty gas seals 3 Visual check of the entire unit 4 Visual check of the combustion process and cleaning of the burners if needed 5 If called for by check no 3 dismantling and c...

Страница 23: ...n the junction box If a room thermostat is not required on Zone 2 insert a link between 6 8 on the junction box V4043H VALVE BROWN 8 BLUE 2 GREY 9 ORANGE 10 GREEN YELLOW 3 Honeywell ST 699B 1002 6 3 N...

Страница 24: ...10 on the junction box If a room thermostat is not requied on Zone 1 insert a link between 4 5 on the junction box If a room thermostat is not requied on Zone 2 insert a link between 6 8 on the junct...

Страница 25: ...NOTES 25 B023...

Страница 26: ...26 B023 NOTES...

Страница 27: ...27 B023...

Страница 28: ...Commercial subsidiary MTS GB LIMITED MTS Building Hughenden Avenue High Wycombe Bucks HP13 5FT Telephone 01494 755600 Fax 01494 459775 Technical Service Hotline 01494 539579 Cod 23 99 84 1260 112 B02...

Отзывы: