47

settings - adjustment - problem identi

fi

 cation menus

SERVICE CODE

222

press the programming 

“+”

   

button to select 234 and press the 

“+” 

OK

 button

220

Soft ignition

from 0 to 99

60

see parag. Gas settings

224

Thermoregulation

0= Absente

1 = Present

0

228

Boiler version 

- NOT TO MODIFY

from 0 to 5

0

ONLY FOR SERVICE - To be used only in substitution P.C.B.

231

Maximum Central Heating 

power Adjustable heating

from 0 to 99

see parag. Gas settings

232

Domestic hot water maximum 

RPM percentage

CANNOT BE MODIFIED

from 0 to 99

RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is 

changed see “gas setting” table

233

Minimum RPM percentage

CANNOT BE MODIFIED

from 0 to 99

RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is 

changed see “gas setting” table

234

Heating maximum RPM 

percentage

CANNOT BE MODIFIED

from 0 to 99

RESERVED FOR TECHNICAL ASSISTANCE Only if the gas or PCB is 

changed see “gas setting” table

236

Anti-cycling time

from 0 to 7 (minutes)

3

247

Central Heating Pressure 

detection device

0 = Temperature

       Probes only

1 = Pressure switch

2 = Pressure sensor

1

ONLY FOR SERVICE - To be used only in substitution P.C.B.

250

CONFORT FUNCTION

0 = Disabled

1 = Time Based

        (30 minute)

2 = Always active

0

The  “COMFORT”  function  of  the  appliance  can  be  used  to 

increase the comfort level of the user when drawing hot water.

This function keeps the secondary exchanger hot during periods 

of  boiler  inactivity;  this  increases  the  initial  heat  status  of  the 

water drawn, as the water is delivered at a higher temperature. 

252

Hot water 

fl

 ow delay

from 5 to 200

 (0.5 to 20 seconds)

5

Anti "water hammering"

253

D.H.W. switch logic

0 = Anti-scale 

       (stop at > 67°C)

1 =  At 4°C over set-

point

0

254

Post-circulation and post-

ventilation after domestic hot 

water is drawn

0 = OFF

1 = ON 

0

OFF  =  3  minutes  post-circulation  and  post-ventilation  after 

domestic hot water draw-o

ff

  if the boiler temperature measured 

requires it.

ON  =  always  on  for  3  minutes  post-circulation  and  post-

ventilation after domestic hot water draw-o

ff

 .

par

ameter

description

value

default setings

notes

270

Test mode

-

 =  Max Heating power

--  

= Max DHW power

-- 

= Minimum power

Enabled also by pressing for 10 seconds the Reset button.  This 

function is deactivated automatically after 10 minutes, or when 

the RESET  button is pressed.

271

Air purge Function

Press MODE button to 

active 

420

Zone 1 Temperature range

0 = from 20 to 45°C

      

(low temperature)

1 = from 35 to 85°C   

     

 (high temperature)

421

Select Type of Thermoregulation 0 = Fixed Flow 

Temperature

1 = Basic 

Thermoregulation

3 = Outdoor 

Temperature only

1

422

Zone 1 Slope

from 0_2 to 0_8

(low temp)

0_5

from 1_0 to 3_5

(hight temp)

1_5

Flow 

Temperature 

Low temperature

High temperature

External temperature

Ambiente temperature

setting value

°C 

20 

25 

15 

30 

40 

50 

60 

70 

80 

90 

100 

°C 

10 

2.5 

3.0 

3.5 

2.0 

1.5 

1.2 

1.0 

0.8 

0.6 

0.4 

0.2 

-5 

-10 

-15 

-20  °C 

When an outdoor sensor is used, the boiler calculates the most 

suitable delivery temperature, taking into account the outside 

temperature and type of system. 

The type of curve should be selected in correspondence with 

the projected temperature of the system and the nature of the 

dispersions present in the structure.

For high-temperature systems, one of the curves depicted 

below may be chosen.

par

ameter

description

value

default setings

notes

Содержание EGIS PREMIUM S 25

Страница 1: ...INSTALLATION AND SERVICING INSTRUCTIONS CONDENSING WALL HUNG GAS BOILER EGIS PREMIUM S HOT WATER I HEATING I RENEWABLE I AIR CONDITIONING...

Страница 2: ...2 3 3 3 4 5 5 6 6 6 7 8 8 8 8 8 9 9 9 9 9 10 10 10 11 11 12 12 13 13 14 15 15 15 15 15 15 16 16 16 18 18 18 19 19 19 20 20 20 20 20 21 22 25 25 26 26 26 26 26...

Страница 3: ...3 CE CE 2009 142 CEE 2004 108 EC 92 42 CEE 2006 95 EC...

Страница 4: ...4...

Страница 5: ...5 OK ESC 1 2 3 4 6 7 5 Reset...

Страница 6: ...6 A B C D E 150 319 180 25 745 28 745 200 120 120 200 65 L 65 67 67 450 0 5 3 0 0 3 50 50 OK ESC 1 2 3 4 5 6 7 9 10 12 14 15 16 17 18 19 20 21 23 24 22 8 13...

Страница 7: ...2 9 0 9 A 0 9 A s s a l c 2 2 2 2 0 0 1 0 0 1 a P 5 5 s s a l c 4 6 5 6 C C 0 9 0 9 1 0 1 m p p 2 O 0 5 4 5 4 4 9 4 h g K C 0 6 C 0 8 7 2 7 2 1 r a b 3 r a b 8 1 3 8 L 2 8 5 3 C 5 4 0 2 C 0 6 6 3 2 8...

Страница 8: ...8 F A B C D E I G H EGIS PREMIUM S 25 EGIS PREMIUM S 31...

Страница 9: ...9 0 1 2 3 4 5 6 7 0 100 200 300 400 500 600 700 800 900 1000 mCE l h EGIS PREMIUM S 25 EGIS PREMIUM S 31 I 15mm interno 22 mm...

Страница 10: ...10 1 3 4 6 7 8 9 10 12 13 14 15 11 16 17 18 19 20 21 22 23 24...

Страница 11: ...33 C43 10 60 100 B33 10 C13 C33 C43 30 80 125 B33 30 S1 S2 C13 26 26 80 80 0 6 0 6 5 1 5 1 C33 50 50 80 80 0 6 0 6 2 2 C43 26 26 80 80 0 6 0 6 5 1 5 1 S1 S2 C53 C83 50 80 80 8 60 60 B23 50 25 12 12 36...

Страница 12: ...12 H05V2V2 F 60 N L...

Страница 13: ...13 a b c d TA2 FLOOR SE SOL TA1 T B TA2 FLOOR SE SOL TA1 CN1 Outdoor sensor Under oor heating thermostat Room Thermostat 1 FLOOR SE SOL TA1...

Страница 14: ...CN4 Bk Bk Gr Wh Rd Bl Bk Bk Br Bl Bk Bl Br CN2 CN11 1 1 CN14 CN3 1 1 CN8 1 CN25 1 N N FLAME L L TA2 FLOOR SE SOL TA1 CN19 CN1 CN4 1 LV HV CN14 CN3 1 1 CN8 CN9 1 1 CN25 1 1 CN6 CN11 1 1 Bk Bk Bk Bk Bk...

Страница 15: ...15 OK ESC...

Страница 16: ...16 2 1 3 2 4 2 4 1...

Страница 17: ...17 3 65 C 1 C02 4 C02 1 5 RESET Gas CO2 MAX G20 9 0 0 7 G31 10 0 0 7...

Страница 18: ...18 31 25 231 220 236 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC OK ESC 1 6...

Страница 19: ...6 0 2 2 0 6 1 3 2 8 1 3 3 2 8 7 4 3 2 6 8 2 3 2 3 4 7 5 m m 3 3 2 7 1 3 7 1 2 6 9 2 0 5 0 9 6 0 25 G20 G31 9 6 0 7 7 6 5 4 55 55 8 1 80 91 6 3 0 5 2 0 2 5 7 2 9 7 1 3 4 2 9 1 0 8 5 0 15 C 1013 mbar 1...

Страница 20: ...20 3 bar EEPROM 15 5 OK ESC...

Страница 21: ...21...

Страница 22: ...22 1 5 222 2 234 3 4 220 5 231 6 70 7 75 8 OK ESC ESC OK ESC 1 6...

Страница 23: ...232 RPM 0 99 233 RPM 0 99 234 RPM 0 99 236 0 7 3 247 0 1 2 1 250 234 OK 422 0_2 0_8 0_5 1_0 3_5 1_5 0 1 30 2 252 5 200 0 5 20 5 253 0 67 C 1 4 C 0 254 0 1 0 270 271 420 0 20 45 C 1 35 85 C 421 0 1 3 1...

Страница 24: ...24 822 rx100RPM 831 C 832 C 842 425 35 85 C 420 1 82 20 45 C 420 0 45 426 35 85 C 420 1 40 20 45 C 420 0 25...

Страница 25: ...25 a c d b...

Страница 26: ...26...

Страница 27: ...supply cable 36 Peripheral unit connection 37 Room Thermostat connection 37 Electrical diagram 38 Commissioning 39 Ignition procedure 39 Initial procedures 39 Electricity supply 39 Filling the hydraul...

Страница 28: ...er leaking from damaged piping Make sure the installation site and any systems to which the appliance must be connected comply with the applicable norms in force Electrocution caused by contact with l...

Страница 29: ...eously allows for accessing the setting adjustment and diagnostics parameters b Pressing the buttons simultaneously allows for modifying and saving the parameter settings Display Legend Digits indicat...

Страница 30: ...th the clearances stated below 1 2 3 4 5 6 7 9 10 12 14 15 16 17 18 19 20 21 23 24 22 8 13 Legend 1 Flue connector 2 Air relief valve 3 Main heat exchanger 4 Detection Electrode 5 C H Return temperatu...

Страница 31: ...stars Sedbuk class class A 90 A 90 Loss when stopped T 50 C Loss of burner gas when operating 2 2 2 2 EMISSIONS Available air pressure Pa 100 100 NoX class class 5 5 Flue gas temperature G20 80 C 60 C...

Страница 32: ...er may be accessed after it has been installed should be respected WARNING No inflammable items should be left in the vicinity of the boiler Make sure the installation site and any systems to which th...

Страница 33: ...re is too high the boiler will stop both do mestic hot water and the heating production and the error code 1 16 oor thermostat contact open will appear on the display The boiler will restart when the...

Страница 34: ...he suction exhaust ducting split connection of the boiler to the exhaust ducting with air suction from outside split connection of the boiler to the exhaust ducting with air suction from the room Prod...

Страница 35: ...ent fixing it in place using the screw provided Table of flue gas exhaust duct lengths S1 Air intake S2 Flue gas exhaust Type Maximum Extension Exhaust air m Diameter of pipe mm EGIS PREMIUM S 24 30 C...

Страница 36: ...e manufacturer is not responsible for any damage caused by the lack of a suitable earthing system or by the malfunctioning of the electricity mains supply Make sure that the system is able to withstan...

Страница 37: ...t 1 Room thermostat connection Introduce the thermostat wire Loosen the cable clamp using a screwdriver and insert the wires leading from the room thermostat one at a time Connect the wires to the ter...

Страница 38: ...e C H Flow temp probe Thermal fuse Thermal fuse D H W flow switch Switch ON OFF Br Rd Rd Bl Bl Br Br Br Bk Bk Bk HV connection N N FLAME L L CN19 CN4 Bk Bk Gr Wh Rd Bl Modulating Fan Detection electro...

Страница 39: ...illing stage or if there is excess air in the system the deaeration cycle can be activated by holding the MODE button for 10 seconds The boiler will start a cycle which lasts approximately 7 minutes W...

Страница 40: ...lowing icon appears on the display gas boiler activated at the C H maximum power Press the button 1 to elect the icon D H W maximum power Wait 1 minute for the boiler to stabilise before carrying out...

Страница 41: ...1 minute after each adjustment for the CO2 value to stabilise WARNING this adjustment is sensitive a rotation of a 1 4 turn corresponds to 0 4 of CO2 Once the CO2 value is close to the values given i...

Страница 42: ...lue e g 75 75 8 Press the OK button to save the change or press ESC to exit without saving To exit press the ESC button until the normal display screen is restored Checking slow ignition power The sof...

Страница 43: ...Example 1 SINGLE ZONE SYSTEM HIGH TEMPERATURE WITH ON OFF ROOM THERMOSTAT In this case the following parameters must be set 4 21 Activation of temperature adjustment using sensors Select 04 Basic temp...

Страница 44: ...the system If this is the case a plumber should be contacted Operation shutdown This type of error is non volatile which means that it is not removed automatically On the display flash Err and the err...

Страница 45: ...to run for two minutes If the flow temperature remains between 4 8 C the pump will con tinue to run for two minutes for a maximum of 10 times unless a temperature above 8 C is detected in the central...

Страница 46: ...f parameters value Programming ESC key to exit from the parameters The information relating to the parameters are indicated on the display Caution The menus reserved for qualified technicians may only...

Страница 47: ...lay from 5 to 200 0 5 to 20 seconds 5 Anti water hammering 253 D H W switch logic 0 Anti scale stop at 67 C 1 At 4 C over set point 0 254 Post circulation and post ventilation after domestic hot water...

Страница 48: ...e decrease in relation to the set point value from 14 to 14 C high temperature from 7 to 7 C low temperature Warning The curves can be shifted upwards or downwards without accessing the parameter usin...

Страница 49: ...external bipolar switch and shut off the gas valve To access the inside of the boiler the following is necessary 1 Loosen the two screws on the front casing a pull it forwards and unhook it from the u...

Страница 50: ...the flue system is sealed and operating correctly Draining procedures The heating system must be drained using the following procedure Switch off the boiler make sure the external bipolar switch is in...

Страница 51: ...gas category 7 Gas setting 8 Installation type 9 Electrical data 10 Maximum domestic hot water pressure 11 Maximum heating pressure 12 Boiler type 13 NOx class Efficiency 14 Input rating nominal heati...

Страница 52: ...ITALIAN DESIGN ariston com Ariston Thermo SpA Viale A Merloni 45 60044 Fabriano AN www aristonthermo it info it aristonthermo com 420010595100...

Отзывы: