Quick Start Guide: 7000 Series 1 RU-Gen 3 Data Center Switches
Connecting Power Cables
Chapter 4: Cabling the Switch
To connect a DC power supply to power source:
Step 1
Remove the terminal cover to expose the connectors on the terminal block on the face.
Step 2
Attach the appropriate lugs to the source DC wires.
Use DC cables with either insulated crimp-on spade lugs or insulated crimp-on ring
connectors.
Important!
Wire size must comply with local and national requirements and electrical codes. Use only copper wire.
Calibre doit respecter les exigences locales et nationales et les codes de l’électricité. Utiliser seulement
du fil de cuivre.
Step 3
Connect the DC-input wires to the terminal block in this order:
1
. Ground cable to the ground connector on the face of the power supply.
2
. Negative (–) source DC cable to the negative (–) connector on the terminal block.
3
. Positive (+) source DC cable to the positive (+) connector on the terminal block.
4.
Torque the screws to 1.0 N·m / 9 in·lb.
Important!
Apply the ground connection first during installation and remove last when removing power.
Appliquer le motif connexion tout d’abord pendant l’installation et supprimer dernière lors du retrait de
puissance.
5.
Replace the terminal cover.