Chapter 4: Cabling the Modular Switch
7500 Series Modular Switch Quick Start Guide
PDOC-00015-07
13
Chapter 4 Cabling the Modular Switch
4.1
Grounding the Switch
After mounting the switch into the rack, connect the switch to the data center ground.
displays the location of the grounding pads located on both sides of the power input sockets.
After the switch is grounded, ESD wrist straps can be grounded by connecting them to one of the ESD
grounding ports located between the power input sockets, (
) or the rear panel (
depicts the location on the 7504. Receptacles are available in similar locations on other switch models).
4.2
Connecting Power Cables
Important!
Installation of this equipment must comply with local and national electrical codes. If necessary, consult
with the appropriate regulatory agencies and inspection authorities to ensure compliance.
The switch operates with four power supplies, each of which connects to circuits that provide 200-240
VAC, 50 or 60 Hz, and 20 A.
• DCS-7508 / 7508E requires the connection of at least two power supplies to active circuits.
• DCS-7504 / 7504E requires the connection of one power supply to an active live circuit.
Connecting power to all four power supplies protects against up to two failed power supplies and can
provide grid-level redundancy. Energizing any power supply causes all power supply fans to function.
Figure 12: Grounding Pad and ESD Grounding Port Sockets
Figure 13: ESD Grounding Port – Rear Panel