Cabling the Switch
Table 5: Wiring, Lug, and Tightening Torques for DC PSUs
Wire Size
Tightening Torque
PSU
(AWG)
(mm2)
Lug Type
N.m
in.lbs
PWR-7010-
DC
12 to 22
3.3 to 0.33
ring
0.8
7.0
PWR-100-DC
14 to 18
1.5 to 0.75
ring
0.8
7.0
4. Replace the terminal cover.
4.3
Connecting Serial and Management Cables
Cables required to connect the device.
The accessory kit includes the following cables:
•
RJ-45 to DB-9 serial adapter cable
•
RJ-45 Ethernet cable
The following RJ-45 to DB-9 table lists the pin connections of the RJ-45 to DB-9 adapter cable.
Table 6: RJ-45 to DB-9 Connections
RJ-45
DB-9
RJ-45
DB-9
RTS
1
8
CTS
GND
5
5
GND
DTR
2
6
DSR
RXD
6
3
TXD
TXD
3
2
RXD
DSR
7
4
DTR
GND
4
5
GND
CTS
8
7
RTS
Figure 11: Front Panel Ports
1
Console serial port
2
Ethernet management port
3
USB port
Connect the front panel ports as follows:
•
Console (Serial) Port: Connect to a PC with the RJ-45 to DB-9 serial adapter cable. The switch
uses the following default settings:
17