10
EG
D
REFRIGERANT CONNECTION BETWEEN EMIX TANK AND OUTDOOR UNIT
•
Close the valves on the port of outdoor unit.
•
For applications “NOT ONLY DHW”: disconnect the bypass from the valves on the Emix port (take care of it in
case of removal of Emix Tank unit).
•
Connect the refrigerant pipes of Emix Tank to the outdoor unit (it is warmly suggested a strong insulation).
On the bottom part you will see two pipes; they are for the refrigerant circuit between the outdoor unit and Emix
Tank, marked with the following label:
R410A, IN (X) is the pipe from the outdoor unit
R410A, OUT (Y) is the pipe to the outdoor unit
Pay the max. attention to respect the sense of these connections, both if you are using Emix Tank connected to
the Emix port or the standard port of the outdoor unit.
•
In case Emix Tank is connected to Emix port:
- connect the port (X) of outdoor unit to the pipe R410A, IN (X) of Emix Tank
- connect the port (Y) of outdoor unit to the pipe R410A, OUT (Y) of Emix Tank
•
In case Emix Tank is connected to a normal port (G30 / G42):
- connect the gas pipe 3/8” of outdoor unit to the pipe R410A, IN (X) of Emix Tank
- connect the liquid pipe 1/4” of outdoor unit to the pipe R410A, OUT (Y) of Emix Tank
Use the adapter indicated in the fi gure.
•
Perform the vacuum procedure.
•
Open the valves of the outdoor unit port where Emix Tank is connected.
R410A, 3/8” IN
R410A, 3/8” OUT
R410A, 3/8” IN
R410A, 3/8” OUT
R410A, 3/8” IN
R410A, 3/8” OUT
G30 / G42 ONLY DHW (SEE SECTION “ONLY DHW APPLICATION”)
Emix Tank
G140
Emix Tank
OTHER OUTDOOR UNITS
Emix Tank
R410A, IN (X)
R410A, OUT (Y)