5-7 Forced Mode
In this mode the system operates (COOLING or HEATING mode – fixed settings) or is switched off by
means of the MODE button of the indoor unit control board. The operation modes can be selected
pressing the button in a cyclic way (OFF
Ö
COOL
Ö
HEAT
Ö
OFF…). The settings are:
COOLING mode
SET POINT temperature = 25°C
FAN SPEED = HIGH
HEATING mode
SET POINT temperature = 21°C
FAN SPEED = HIGH
5-8 Protection operations in Cool and Dry Mode
This protection prevents ice formation on the indoor coil heat exchanger. The protection is activated by
the indoor coil temperature (ICT sensor) and only after 6 minutes of compressor operation. This
protection acts in 2 levels:
LEVEL 1
INDOOR FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: ON
OUTDOOR FAN: cycling (30 seconds ON
B
30 seconds OFF).
LEVEL 2
INDOOR FAN SPEED: ANY (as selected from remote controller)
COMPRESSOR: OFF for at least 6 minutes and until ICT
≥
8°C
OUTDOOR FAN: OFF for at least 6 minutes and until ICT
≥
8°C
The system exit this protection routine when ICT temperature rises above 8°C.
22
Содержание AW720HL
Страница 11: ...2 DIMENSIONAL DATA AW720HL AW726HL AW735HL AW726CL AW735CL AW720 726 12 7 1 2 AW735 11...
Страница 12: ...AW726HLF AW735HLF AW726CLF AW735CLF...
Страница 16: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams HEAT PUMP MODELS COOLING MODELS 16...
Страница 17: ...4 2 Wiring System Diagram HEAT PUMP MODELS COOLING MODELS 17...
Страница 32: ...6 5 SOME PARTS OF THE AIR CONDITIONER DO NOT OPERATE 32...
Страница 33: ...6 6 AIR CONDITIONER OPERATES BUT ABNORMALITIES ARE OBSERVED 33...
Страница 34: ...34...
Страница 35: ...6 7 POOR COOLING OR HEATING 35...
Страница 36: ...6 8 EXCESSIVE COOLING OR HEATING 6 9 A SENSOR IS DEFECTIVE 36...
Страница 39: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima com...