7
EG
TUBING LENGTH AND ELEVATION DIFFERENCE LIMITS
No additional charge of compressor oil is necessary.
L Tot. = Total tubing length (L1 + L2 + L3...)
Ln =
Maximum tubing length of a single indoor unit (n=1,2,3...)
L =
Keep Emix tubing as short as possible (MAX. 10/12m)
REQUIRED AMOUNT OF ADDITIONAL REFRIGERANT
For tubing 1/4 “ - 3/8” = 15g/m
For tubing 1/4 “ - 1/2” = 20g/m
For tubing Emix (1/2”) = 20g/m
LIMIT OF ELEVATION DIFFERENCE - OUTDOOR UNIT/INDOOR UNIT: 10m (H1, H2, H3, H4, H5, H6)
LIMIT OF ELEVATION DIFFERENCE BETWEEN INDOOR UNITS: 5m (H)
1.Standard screwdriver
2.Phillips head screwdriver
3.Knife or wire stripper
4.Tape measure
5.Level
6.Sabre saw or key hole saw
7.Hacksaw
8. Core bits ø 5
1
9.Hammer
10.Drill
11. Tube cutter
12.Tube flaring tool
13.Torque wrench
14.Adjustable wrench
15.Reamer (for
reburring)
16.Hex. key
Tools required for installation (not supplied)
1.
REDUCTION 1/2F - 3/8M + PIPE UNION 3/8 (2pcs)
2.
REDUCTION 3/8F - 1/2M + PIPE UNION 1/2 (2pcs)
3.
COVER (11pcs)
4.
DRAIN TUBE
5.
ADHESIVE DAMPER (4pcs)
6.
TUBES 1/4 - 3/8 + 1/2 - 5/8 for HK (1set)
ACCESSORIES SUPPLIED WITH THE UNIT
2
4
1
3
MINIMUM LENGTH
L Tot. (m)
L n (m)
L Tot. (m)
L n (m)
L (m)
MONO SPLIT
40
-
50
-
5
DUAL SPLIT
40
30
100
30
5
AEI1G140
TRIAL SPLIT
40
30
100
30
5
QUADRI SPLIT
40
30
100
30
5
PENTA SPLIT
40
30
100
30
5
AT SHIPMENT
ADDITIONAL REFRIGERANT
5
6
REGULATION (EU) No. 517/2014 - F-GAS
The unit contains R410A, a fluorinated greenhouse gas with
a global warming potential (GWP) of 2087.50. Do not
release R410A into the atmosphere.
R410A: 4.40 kg / 9.19 Tonn.CO2
Содержание AEI1G140 3PH
Страница 12: ...GIG 4 2 INDOOR UNITS 3 INDOOR UNITS POWER SUPPLY AC 380 415V 3PHASE 50Hz POWER SUPPLY AC 380 415V 3PHASE 50Hz ...
Страница 20: ...4 FG 2 INDOOR UNITS 3 INDOOR UNITS POWER SUPPLY AC 380 415V 3PHASE 50Hz POWER SUPPLY AC 380 415V 3PHASE 50Hz ...
Страница 28: ...DG 4 2 INDOOR UNITS 3 INDOOR UNITS POWER SUPPLY AC 380 415V 3PHASE 50Hz POWER SUPPLY AC 380 415V 3PHASE 50Hz ...
Страница 36: ...EG 4 2 INDOOR UNITS 3 INDOOR UNITS POWER SUPPLY AC 380 415V 3PHASE 50Hz POWER SUPPLY AC 380 415V 3PHASE 50Hz ...
Страница 44: ...PG 4 2 INDOOR UNITS 3 INDOOR UNITS POWER SUPPLY AC 380 415V 3PHASE 50Hz POWER SUPPLY AC 380 415V 3PHASE 50Hz ...
Страница 52: ...GGR 4 2 INDOOR UNITS 3 INDOOR UNITS POWER SUPPLY AC 380 415V 3PHASE 50Hz POWER SUPPLY AC 380 415V 3PHASE 50Hz ...
Страница 62: ...14 9 ASID ASIC 10 EMIX PORT SEE EMIX UNIT OR EMIX TANK INSTALLATION MANUAL ASIC 11 ...
Страница 63: ...15 12 ASID ASIC 13 EMIX PORT SEE EMIX UNIT OR EMIX TANK INSTALLATION MANUAL 14 ...
Страница 65: ...17 ...
Страница 85: ...37 ...
Страница 86: ......
Страница 87: ......