– I-76 –
Shield for Upward Exhaust Discharge
Wind Shield for low ambient models
It is necessary for you to install an air discharge
chamber (field supply) to direct exhaust from the fan
upward if:
it is difficult to provide a space of min. 50 cm
between the air discharge outlet and a obstacle.
the air discharge outlet faces a walkway where it
may blow warm air onto passersby.
Refer to Fig. right.
It is recommended to use wind shields for models with
“—L” inside model numbers. Low ambient models
are designed to use in low outdoor temperature condi-
tions.
General
When the outdoor unit is installed in a position ex-
posed to strong wind (like seasonal winds with low air
temperature in winter), wind shields must be installed
on the outdoor unit.
This unit is designed so that the fan of the outdoor unit
runs at low speed when the air conditioner is operated
at low outdoor air temperatures. When the outdoor unit
is exposed to wind, wind influences operating pressure
and causes unstable operation such as activation of high
pressure switch or freeze prevention.
Install a pair of wind shields at the front and back of
the outdoor as required on the upwind side only or on
both sides.
Wind
Wind
Wind shield
(air intake side)
Wind shield
(air discharge side)
Back
Front
0555_C_I
Air discharge
0426_C_I
Important
1546_C_I
3 - ø40 hole
6 - ø6 hole
250
549
24
132
570
13
596
554
131
250
250
27
554
1545_C_I
3 - ø60 hole
8 - ø6 hole
450
100
250
250
1116
132
567
131
300
Bottom plate
Bottom plate
592
For 525 type
For 536, 548 type
Recommended outer dimensions of wind shield
(field supply)
* In snow areas, bottom plate should be removed.