![Argo AC 425 C Скачать руководство пользователя страница 5](http://html.mh-extra.com/html/argo/ac-425-c/ac-425-c_technical-data-and-service-manual_2967424005.webp)
– I-3 –
MODEL No. Indoor Unit AS 425C
Outdoor Unit AER525SC3E
POWER SOURCE
380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE
Cooling
Capacity
kW
7.3
BTU / h
25,000
Air circulation (Hi / Me / Lo)
m
3
/h
1,140 / 1,020 / 840
Moisture removal (High)
Liters/h
3.6
ELECTRICAL RATINGS
Voltage rating
V
380
400
415
Available voltage range
V
342 – 456
Running amperes*
A
4.82
4.78
4.73
Max. running amperes**
A
5.67
5.68
5.69
Power input
kW
2.76
2.79
2.82
Power factor
%
87
84
83
C.O.P
W / W
2.64
2.62
2.59
Max. starting amperes
A
27
29
30
FEATURES
Controls / Thermostat control
Microprocessor
Timer
ON / OFF 12-hours
ON/OFF 24-hours & Program
Fan speeds Indoor / Outdoor
3 and Automatic control / 2 (Auto)
Airflow direction (Indoor)
Automatic (Remote control)
Air filter
Washable, easy access, long life (2,500 hr)
Remote controller (Option)
Wired : RCS-31G(W)
Wireless : RCS-5PS3E
Refrigerant control
Capillary tube
Drain pump (Drain connection)
Max. head 25 cm above drain connection (25A, OD32 mm)
Compressor
Rotary (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A
37 / 35 / 31
Outdoor - Hi
dB - A
52
Color (Approximate value)
Indoor
Munsell 10Y9.3 / 0.4, RAL 9010-GL
Outdoor
Munsell 6.96Y8.13 / 0.2, RAL 7035-GL
REFRIGERANT TUBING
Limit of tubing length
m (ft.)
40 (131 )
Limit of tubing length at shipment
m (ft.)
15 ( 49 )
Limit of elevation difference
m (ft.)
Outdoor unit is higher than indoor unit : 40 (131)
between the two units
Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube
Narrow tube
mm (in.)
6.35 (1 / 4)
outer diameter
Wide tube
mm (in.)
15.88 (5 / 8)
Refrigerant amount at shipment
kg
R407C - 2.4
DIMENSIONS & WEIGHT
Indoor unit (Include panel)
Outdoor unit
Unit dimensions
Height
mm (in.)
328 ( 12 - 29 / 32)
735 (28 - 30 / 32)
Width
mm (in.)
860 ( 33 - 27 / 32)
940 (37
)
Depth
mm (in.)
860 ( 33 - 27 / 32)
340 (13 - 12 / 32)
Package dimensions
Body
Panel
Outdoor unit
Height mm (in.) 284 (11 - 6 / 32)
104 ( 4 - 3 / 32)
826 (32 - 17 / 32)
Width mm (in.)
824 (32 - 14 / 32)
967 (38 - 2 / 32)
1,016 (40
)
Depth mm (in.)
833 (32 - 25 / 32)
999 (39 - 11 / 32)
416 (16 - 12 / 32)
Net weight
kg (lb.)
30 (66)
67 ( 148)
Shipping weight
kg (lb.)
27 ( 60 )
8 ( 18 )
73 ( 161 )
Shipping volume
m
3
(cu. ft)
0.195 ( 6.9 )
0.1 ( 3.5 )
0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*):
Indoor air temperature 27
°
C DB / 19
°
C WB, Outdoor air temperature 35
°
C DB
Full load conditions (**): Indoor air temperature 32
°
C DB / 23
°
C WB, Outdoor air temperature 43
°
C DB