6-2 Dry Mode Operation
Dry operation remove moisture from indoor air running, in cooling mode, at a low level without reducing the
ambient temperature. This is done cycling ON and OFF indoor and outdoor units according to below.
SPT = Set Point Temperature
6-3 Fan Mode Operation
With this mode, the indoor fan is turned ON while CM and FMO stay OFF all the time. The user can select
between 4 speeds: HIGH, MEDIUM and LOW.
6-4 Auto Fan Speed
With this option selected, the indoor fan speed changes automatically according to the difference between
the detected air temperature (RAT sensor) and the set point (SPT):
COOLING MODE
2
≤
(RAT – SPT):
HIGH speed
1
≤
(RAT – SPT)
<
2:
MEDIUM speed
(RAT – SPT)
<
1:
LOW speed
NOTE
SPT = Set Point Temperature
ROOM
TEMPERATURE
DRY LEVEL
< SPT-1°C
≥
15°C
LEVEL 2
≥
SPT+2°C
LEVEL 0
< 15°C
DRY OFF ZONE
CM OFF
FMO OFF
FMI OFF
CM switches 9 minutes OFF and 3 minutes ON
FMO switches 9 minutes OFF and 3 minutes ON
FMI switches OFF and L during CM operation
< SPT+2°C
≥
SPT-1°C
Operation according to COOLING mode
LEVEL 1
CM ON
FMO ON
FMI switches between L and OFF (30 seconds)
12
Содержание 39.7028.942
Страница 7: ...2 DIMENSIONAL DATA 2 1 Unit Dimensions A E C B D F A B C D E F 245 525 490 250 790 580 AUG38PCLI 7 ...
Страница 8: ...3 REFRIGERANT FLOW DATA 3 1 Refrigerant Flow Diagram 8 ...
Страница 21: ...E SOME PARTS OF THE AIR CONDITIONER DO NOT OPERATE 21 ...
Страница 22: ...F AIR CONDITIONER OPERATES BUT ABNORMALITIES ARE OBSERVED 22 ...
Страница 23: ...23 ...
Страница 24: ...G POOR COOLING OR HEATING 24 ...
Страница 25: ...H EXCESSIVE COOLING OR HEATING I A SENSOR IS DEFECTIVE 25 ...
Страница 26: ...11 CHECKING ELECTRICAL COMPONENTS 26 ...
Страница 27: ...27 ...
Страница 28: ...Via Varese 90 21013 Gallarate VA Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima com ...