33
Re-assembly of the drive rods for the poles
Leading pole
Led pole
With the aid of the lever
supplied with the parts, without
forcing it, bring the new pole
into position in the tripped
stop" position.
Supplied lever
Grease the pins for each
articulation.
Position the drive rod for the
poles, the oblong hole opposite
the leading pole.
01
Check the positioning in
accordance with the instructions
on the adjustments sheet ref.
470133: the plug gauge must not
penetrate into the passageway
for the pin.
If this is the case, consult our
After Sales Dept. (See §1.1).
S
Example:
S < 6 mm for FP61, 62, 63, 71, 72
Connect the control
mechanism's linkage rod.
Check the position of the pins
in relation to the markings
made when dismantling.
All of the existing clamps
must be replaced by the new
ones supplied.
10.11 Re-assembly of the accessories
- If needed connect the pressure
switch wiring.
- Re-assemble the accessories,
deflectors and screens where
needed.
10.12 Resetting the pole under nominal pressure
Proceed with filling the pole with
SF6 gas to its nominal pressure in
compliance with the value indicated
on the rating plate (See § 7).
10.13 Commissioning the circuit breaker
Proceed with a thorough cleaning
of the insulators with a dry clean
cloth.
Check the presence of safety
clamps on the linkages and of the
free functioning of the assembly.
Ensure that no tool or object has
been forgotten and left on the
circuit breaker.
Proceed with a mechanical
operation test.